Report by zone – SilentKnight Special Instructions for Silent Knight User Manual
Page 3

3
Report by Zone
Configuring the Fire Panel to “Report by Zone” actually handles most events correctly where
zone information is sent in the 3-digit Contact Field. .
Note: AlarmNet assigns and uses separate account numbers from the Fire Panel
AlarmNet Receiver Output
5820XL, 5808, and 5700 Fire Panel
Contact ID data:
Panel Report by Zone:
[10]00s9990s18sE110s00sC001s[13]
Fire Alarm Pt. 43 Module 33-Internal SLC-Zone 1
[10]00s9990s18sR110s00sC001s[13]
Restore Fire Alarm Pt. 43 Module 33-Internal SLC-
Zone 1
[10]1As3456s18sE200s00sC002s[13]
Supervisory Detector Pt. 62 Module 33-Internal
SLC- Zone 2
[10]1As3456s18sR200s00s C002s[13]
Restore Supervisory Detector Pt 62 Module 33-
Internal SLC- Zone 2
[10]1As3456s18sE115s00sC003s[13]
Manual Pull Pt. 01 Module 33- Internal SLC- Zone
3
[10]1As3456s18sR115s00s C003s[13]
Restore Manual Pull Point 01 Module 33- Internal
SLC- Zone 3
[10]1As3456s18sE113s00sC004s[13]
Water Flow Pt. 02 Module 33- Internal SLC- Zone 4
[10]1As3456s18sR113s00s C004s[13]
Restore Water Flow point 02 Module 33- Internal
SLC- Zone 4
[10]00s9990s18sE320s01sC015s[13]
NAC Trouble Circuit 2 Module 34 Internal Supply
Group 15
[10]00s9990s18sR320s01sC015s[13]
Restore NAC Trouble Circuit 2 Module 34 Internal
Supply Group 15
System Events
[10]00s9990s18sE302s00sC034s[13]
Battery Trouble Module 34 Internal Supply
[10]00s9990s18sR302s00sC034s[13]
Restore Battery Trouble Module 34 Internal Supply
This document is not intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticipate all
requirements. All specifications are subject to change without notice. For more information, contact
Silent Knight 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161,
Fax: (203) 484-7118. www.silentknight.com.