Figure 3. interFace tWo-Wire conventional detectorS, nFpa Style B:

(+)

(–)

(+)

(–)

(+)

(–)

+

LISTED BATTERY-BACKUP SWITCHED

REGUALTED DC POWER SUPPLY

POWER TO THE INTERFACE

MODULE MUST BE EXTERNALLY

SWITCED TO RESET THE

DETECTORS. A RELAY CONTROL

MODULE CAN BE USED TO SWITCH

POWER FROM A STANDARD POWER

SUPPLY (SEE FIGURE 5).

OPTIONAL BRANCH CIRCUIT

TO NEXT INTERFACE

MODULE. MODULE

SUPERVISES SUPPLY

VOLTAGE AND

DETECTOR LOOP.

(+)

(–)

TERMINAL WIRING MUST

BE POWER LIMITED.

TO NEXT

DEVICE

INTERFACE

MODULE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO

LISTED COMPATIBLE

CONTROL PANELS ONLY.

FROM

PANEL OR

PREVIOUS

DEVICE

3.9K EOL

RESISTOR

(INCLUDED)

A2143-10

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS MUST

BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT

ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

+

DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY,

OR SECURITY DEVICES ON THE SAME MODULE.

C1061-00

Figure 4. interFace tWo-Wire conventional detectorS, nFpa Style d:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

LISTED

BATTERY-BACKUP

SWITCHED REGUALTED

DC POWER SUPPLY

POWER TO THE INTERFACE

MODULE MUST BE

EXTERNALLY SWITCED TO

RESET THE DETECTORS. A

RELAY CONTROL MODULE CAN

BE USED TO SWITCH POWER

FROM A STANDARD POWER

SUPPLY (SEE FIGURE 5).

OPTIONAL BRANCH CIRCUIT

TO NEXT INTERFACE MODULE.

MODULE SUPERVISES SUPPLY

VOLTAGE AND

DETECTOR LOOP.

TERMINAL WIRING MUST

BE POWER LIMITED.

3.9K EOL RESISTOR

REQUIRED AT TERMINALS

8 & 9 (INCLUDED) A2143-10

DO NOT LOOP WIRE UNDER TERMINALS. BREAK ALL WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS. DETECTORS

MUST BE UL LISTED COMPATIBLE WITH MODULE. INSTALL DETECTORS PER MANUFACTURER’S INSTALLATION INSTRUCTIONS

INTERFACE

MODULE

TO NEXT

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO

LISTED COMPATIBLE

CONTROL PANELS ONLY.

FROM

PANEL OR

PREVIOUS

DEVICE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT

ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

+

+

DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY

DEVICES ON THE SAME MODULE.

C1062-00

Figure 5. relay control Module uSed to diSconnect a poWer Supply:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO LISTED COMPATIBLE

CONTROL PANELS ONLY.

FROM

PANEL OR

PREVIOUS

DEVICE

RELAY CONTROL

MODULE

TO NEXT

DEVICE

POWER LIMITED DC

POWER SUPPLY,

LISTED FOR FIRE

PROTECTION WITH

BATTERY BACKUP

*NOTE: ANY FAULT IN THE POWER SUPPLY IS

LIMITED TO THAT ZONE AND DOES NOT

RESULT IN A FAULT IN A SEPARATE ZONE.

C0945-00

SK-460-012