Mounting
The SK-Zone mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 2

1

/

8

inches. Surface mounted electri-

cal boxes (SMB500) are available from Silent Knight
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power-limited wiring only.

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in

Figure 2.

Figure 2. Module Mounting:

ISOLATED

QUADRANT

C1066-00

SK-460-012

1

I56-3440-001

SK-Zone interface Module

BeFore inStalling
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
general deScription
The SK-Zone Interface Module is intended for use in intelligent, two-wire
systems, where the individual address of each module is selected using the
built-in rotary switches. This module allows intelligent panels to interface and
monitor two-wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors back to the
control panel. All two-wire detectors being monitored must be UL compatible
with this module.
coMpatiBility requireMentS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel only (list available from Silent Knight).
Figure 1. controlS and indicatorS:

C1059-00

SpeciFicationS
Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

5.1 mA (LED on)

Average Operating Current:

270µA (LED flashing)

EOL Resistance:

3.9K Ohms

Maximum IDC Wiring Resistance:

25 Ohms

External Supply Voltage (between Terminals T10 and T11)
DC Voltage:

Regulated 24 VDC

Ripple Voltage:

0.1 Volts RMS maximum

Current:

90mA per module

Temperature Range:

32˚F to 120˚F (0˚C to 49˚C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

/

2

˝ H × 4˝ W × 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

I56-3440-00

1

inStallation and Maintenance inStructionS

12 Clintonville Road, Northford, CT 06472

203.484.7161; Fax: 203.484.7118

www.silentknight.com

coMpatiBle tWo-Wire SySteM SenSor SMoKe detectorS For uSe With SK-Zone interFace Module With Zone identiFier a:

Detector

Compatibility

Detector

Base

Base

Max

Model

ID

Type

Model

Identifier

Detectors

1451

A

Ionization

B401/B

A

20

2451

A

Photoelectric

B401/B

A

20

2451TH

A

Photoelectric with Thermal

B401/B

A

20

1400

A

Ionization

N/A

20

2400

A

Photoelectric

N/A

20

2400TH

A

Photoelectric with Thermal

N/A

20

1100

A

Ionization

N/A

20

1151

A

Ionization

B110LP/B401

A

20

2100

A

Photoelectric

N/A

20

2100T

A

Photoelectric with Thermal

N/A

20

2151

A

Photoelectric

B110LP/B401

A

20

*Used in combination with MTL isolator model MTL3043.