SilentKnight SD505-6SB 6 Sounder Base User Manual
Wiring, Specifications, Slc wiring
![background image](/manuals/711179/1/background.png)
P/N 151191
SD505-6SB 6” Sounder Base
Installation Instructions
This sheet is intended to be used to install the
SD505-6SB to a Silent Knight Addressable
control panel. Refer to the control panel
installation manual for programming
instructions (P/N 151139 or 151209).
The SD505-6SB adds an audible output function
to a Silent Knight addressable detector.
Specifications
Wiring
This section contains instructions to wire the
SD505-6SB to the FACP, and auxiliary power.
For system supervision of terminals, do not use
looped wire under the terminals. Break the wire
run to provide supervision of connections. See
Figure 3.
SLC Wiring
The SD505-6SB can be connected to the FACP
for either Class B (Style 4) or Class A (Style 6)
supervision. Connect the SD505-6SB to the
FACP as shown in Figure 1 or Figure 2.
Figure 1: Class B (Style 4) Wiring
Figure 2: Class A (Style 6) Wiring
Figure 3: Correct wiring methods
Parameter
Rating
Operating Voltage:
SLC Loop 32 VDC
Aux. Input 24 VDC
Aux. Input Power
Current:
Standby:
1 mA
Alarm:
34.3 mA
SLC Current Draw for
Battery Calculation:
Standby:
.082 mA
Alarm:
.082 mA
Operating Temperature:
32° - 120° F
(0° - 49° C)
Humidity:
10-85% RH
Max. SLC Loop Resistance:
50
Ω
Document Outline
- SD505-6SB 6” Sounder Base Installation Instructions
- Wiring
- SLC Wiring
- Auxiliary Power Wiring
- Auxiliary Power Using Flexput™ Circuits
- 1. Connect the aux power wires to the Flexput terminals using “X” terminals as positive, and “O” terminals as negative power. See Figure 5.
- 2. Configure the auxiliary power output for constant output through programming (refer to Section 7.4 of the IntelliKnight 5820XL or IFP-1000 Analog/Addressable Fire System (P/Ns 151209 & 151139).
- Mounting
- Figure 6 : Mounting the SD505-6SB
- 1. Mount the extension base using the #8 1-1/2 screws through any of the extension base mounting holes. (See Figure 6.)
- 2. Connect Aux power and the SLC loop as shown in Figure 1, Figure 2 and Figure 4.
- 3. Connect wiring harness (P/N 140675) to the smoke base and SD505-6SB as shown in Figure 6.
- 4. Attach the smoke base to extension base (P/ N 120505) using the #8 1/2” screws, through the smoke base mounting standoffs. (See Figure 6.)