Form RZ-NA-I-OPT-GR, Page 2

©2004 Thomas & Betts Corporation, All rights reserved.

Printed in the U.S.A.

MANUFACTURER OF GAS, OIL, ELECTRIC HEATING AND VENTILATING SYSTEMS

0904 POD OG

Form RZ-NA-I-OPT-GR

Installation Instructions (cont'd)

4. Leak Test the Gas Connections and Test

the Gas Pressure

If the unit has a gas train that includes an

inlet manual shutoff valve, close the valve.

If the gas train does not include a manual

shutoff valve before the main control valve,

disconnect and cap the gas line.

WARNING: All components of a
gas supply system must be leak
tested prior to placing equipment
in service. NEVER TEST WITH
AN OPEN FLAME.

High pressure testing of supply lines
is acceptable, provided the supply line
has been disconnected from the unit
and the pipe end capped.

Connect a manometer to the outlet pressure

tap.
Turn on the gas supply and leak test the regu-

lator connections. Test using a leak-detect-

ing solution.
Check the gas pressure reading on the ma-

nometer. Outlet gas pressure must not be

greater than 1/2 psi (14" w.c.). Outlet gas

pressure may be adjusted between 4" w.c.

and 12" w.c. at the regulator.

Capacities for Spring Loaded Gas Pressure Regulators, Maxitrol Models 210DZ and 210EZ
- Cubic Feet per Hour (0.64 specific gravity - natural gas)

TABLE 1 - Maxitrol Model 210DZ, 1"

Inlet

Outlet Pressure ("w.c.)

Pressure

2

4

6

9

12

8.0" w.c.

2,400

1,900

1,300

0.5 psi

3,400

3,100

2,700

2,200

0.75 psi

3,500

4,000

3,800

3,400

2,900

1.0 psi

3,500

4,000

4,500

4,300

3,900

1.5 psi

3,500

4,000

4,500

4,800

4,800

2.0 psi

3,500

4,000

4,500

4,800

4,800

3.0 psi

3,500

4,000

4,500

4,800

4,800

5.0 psi

3,500

4,000

4,500

4,800

4,800

TABLE 3 - Maxitrol Model 210EZ, 1-1/2"

Inlet

Outlet Pressure ("w.c.)

Pressure

2

4

6

9

12

8.0" w.c.

4,450

3,650

2,550

0.5 psi

6,300

5,750

5,150

4,050

0.75 psi

7,000

7,500

7,050

6,300

5,450

1.0 psi

7,000

8,800

8,500

7,950

7,250

1.5 psi

7,000

8,800

8,800

10,450

9,950

2.0 psi

7,000

8,800

8,800

10,500 10,500

3.0 psi

7,000

8,800

8,800

10,500 10,500

5.0 psi

7,000

8,800

8,800

10,500 10,500

(4)Pipe Nipple

(3)Elbow (point away from regulator)

(2)Pipe Nipple

(5)Elbow (point

downward)

(6)Pipe Nipple

(7)Attach Screen either

here or on extended

vent line (Vent must

terminate outdoors.)

(1)Hex Bushing

GAS FLOW

3. Install Vent Line (See Figure 1)

Remove the plastic plug from the tapped vent in the top of the regulator. Start-

ing at the regulator (tapped vent) install the vent line by connecting the pieces

of pipe in the following sequence:

Black Iron Hex Bushing

2-1/2" Pipe Nipple

90

°

Elbow (pointing away from the regulator)

2-1/2" Pipe Nipple

90

°

Elbow (pointing downward)

2-1/2" Pipe Nipple

Outdoor Installation

- Attach plastic bug screen.

Indoor Installation

- Extend vent line outdoors using 1/8" field-supplied pip-

ing; attach bug screen to outdoor end of the vent line.

Figure 1- Install vent

line on the gas

regulator in the

sequence and direction

illustrated (If indoor

installation, vent line

must be field extended

to the outdoors.)

TABLE 2 - Maxitrol Model 210DZ, 1-1/4"

Inlet

Outlet Pressure ("w.c.)

Pressure

2

4

6

9

12

8.0" w.c.

3,000

2,400

1,700

0.5 psi

4,000

3,900

3,400

2,700

0.75 psi

4,000

5,000

4,700

4,200

3,700

1.0 psi

4,000

5,000

5,000

5,300

4,900

1.5 psi

4,000

5,000

5,000

6,000

6,000

2.0 psi

4,000

5,000

5,000

6,000

6,000

3.0 psi

4,000

5,000

5,000

6,000

6,000

5.0 psi

4,000

5,000

5,000

6,000

6,000

TABLE 4 - Maxitrol Model 210EZ, 2"

Inlet

Outlet Pressure ("w.c.)

Pressure

2

4

6

9

12

8.0" w.c.

5,150

4,200

2,950

0.5 psi

7,250

6,650

5,950

4,700

0.75 psi

8,000

8,650

8,150

7,250

6,300

1.0 psi

8,000

10,000

9,850

9,150

8,400

1.5 psi

8,000

10,000 10,000 12,000 11,500

2.0 psi

8,000

10,000 10,000 12,000 12,000

3.0 psi

8,000

10,000 10,000 12,000 12,000

5.0 psi

8,000

10,000 10,000 12,000 12,000