beautypg.com

Warn ing – Reznor R6GN Option - Installation - Power Exhaust User Manual

Page 2

background image

Down Flow Application

3a. Install the power exhaust where relief

hood was mounted using same holes and
screws from step 2.

POWER EXHAUST

UNIT

FRESH AIR HOOD

BAROMETRIC RELIEF HOOD

Fig ure 3

IN STAL LA TION

IN STRUC TION

INSTALLATION INSTRUCTIONS FOR

555622 / 555623

POWER EXHAUST USED WITH GR4GM-150/180 (R-22)

and R6GN-150/180 (R410A) UNITS

For GR4GM-150/180 (R-22) Models - Locate plug on the side of the economizer under economizer controls, insert
bushing, and route power exhaust control and supply wiring through economizer side panel. Connect to unit per
accessory wiring diagram. Power exhaust low voltage control wiring connects to EF and EF1 on the economizer W7212
logic module. Refer to the installation instructions provided with the economizer for proper set up and operation.
IMPORTANT: See unit rating label before operating this accessory to ensure correct field supply wire size has
been installed for proper operation.

For R6GN-150/180 (R410A) Models - Application of this accessory on R6GN-150/180 models requires a separate
branch circuit for proper operation.

Locate plug on the side of the economizer under economizer controls, insert bushing,

and route power exhaust control wiring through economizer side panel and connect to unit per accessory wiring diagram.
Power exhaust low voltage control wiring connects to EF and EF1 on the economizer W7212 logic module. Refer to the
installation instructions provided with the economizer for proper set up and operation. Removal of the 6 pin/4 wire harness
assembly from the LINE side of the power exhaust contactor is required prior to field wire attachment. See Table 1 or the
accessory rating label for proper branch circuit electrical requirements. (Field Supplied)

4.

Elec tri cal Con nec tions

Warn ing:

All electrical wiring must comply with the latest edition
of the National Electrical Code (NEC) - NFPA 70.