Form I-CAUA-MB, P/N170640R2, Page 3

Depending on the installation, the cover may be in the correct position or it may need

to be moved. If the cover needs moved, remove the screws, position the cover over

the return air opening that will not be used, and attach using the same screws.

Installation NOTE: Depending on which return air opening is being covered, you may

want to wait to re-attach the cover after the mixing box is attached in Step 4.

4. Attach the Mixing Box

On the rear of the heater, remove the row of screws along the bottom (save the

screws). Position the mixing box against the rear of the heater. If installing a mixing

box with two dampers, remove one or both access panels on the ends of the box.

If only one damper, reach through the return air opening or remove end panel(s).

Reaching inside the mixing box, replace the screws attaching the bottom edge of the

mixing box to the heater.
Using the holes drilled in Step 2, attach both sides and across the top with the sheet-

metal screws provided.

5. Adjust the Damper Linkage - Applies to Mixing Boxes with both

Outside & Return Air Dampers (GA4, GA5, GA6, GA7, GA8, GA9)

Both dampers are closed for shipping. The linkage for the return air damper must be

adjusted prior to use. Follow instructions to adjust damper linkage.

1) Remove the access panel on the end of the mixing box where the damper

controls are located.

2) Loosen the setscrew on the return air damper rod at the damper arm.

3) Manually open the return air dampers. While the dampers are opening, the

damper rod and arm will automatically move to its correct position.

4) Tighten the setscrew.

5) Replace the end panel.

6. Connect the Damper Motor Wires

Wiring depends on the motor and control options selected. See explanation of damper

controls on page 4.

Wiring Instructions:

1) Remove the door panel on the front of the heater. Run the wires from the

damper motor into the heater cabinet, up past the side of the burner box (the

same side as the blower motor wires), and into the control compartment.

2) Refer to the wiring diagram with the heater and attach the wires to the

terminals indicated.

3) Replace the heater door panel.

7. I

nstallation of the optional mixing box is complete. Follow the instructions in the

heater installation manual to complete the installation of your heater.
Attach the outside air ductwork to the duct flange on the outside air inlet of the mixing

box. If the system includes return air ductwork, attach it to the duct flange on the return

air inlet. To reduce noise transmission, use of a flexible duct boot to attach ductwork is

recommended. Ductwork must be supported; do not rely on the mixing box to support

the ductwork.
On startup, check for proper operation of the damper motor and controls.

Damper Controls -

In all cases when the

unit shuts down, the

outside air damper

closes.

Option Description

Damper Motors (Actuators)

GB2

2-position damper motor

GB3

Modulating damper motor

GB4

Modulating damper motor for use with proportional enthalpy control only

Control Options (Cause motor to operate damper.)

GC1A Potentiometer on mixing box

GC1B Remotely located potentiometer

GC3A Mixed air temperature controller, heating only

GC3B Dual setpoint modulating enthalpy control for heating & cooling, w/GB4 only

GC3C 2-position enthalpy control to use w/2-position damper motor, cooling only
GC4

Senses return air temperature to delay opening of outside air damper

providing warm up or cool down time