Installation instructions (cont’d) – Reznor ZQYRA Option - Installation - Remote Display User Manual
Page 4
I-ZQYRA RB5 Display, P/N 260737, page 4
www.ReznorHVAC.com
(800) 695-1901
©2014 Reznor, LLC. All rights reserved.
Trademark Notes: Reznor
®
is registered in at least the United States.
All other trademarks are the property of their respective owners.
0514 Form I-ZQYRA RB5 Display (Version 0.1)
c) The list of terminals associated with main control module is set at the factory and
should not need to be adjusted. If access is needed, the following procedure can
be used.
Access configuration mode on the remote display (press
UP
,
DOWN
,
and
ENTER buttons and hold all three for at least 5 seconds). NOTE: The
I/O Board Address” field should remain at the default setting of “01”. Press the
ENTER button four times to bypass the display address screen and move to
the terminal configuration screen as shown below. This screen tells the controller
what each of the terminal addresses are. The first terminal should be at 32 and
the second terminal will be at 31.
To exit the configuration procedure and save the data, select the “OK?” field, set
“Yes”, and confirm by pressing the
ENTER button.
7. Check the remote display for proper operation.
Installation
Instructions
(cont’d)