Refrigerant pipe connection, 16 refrigerant pipe connection – Perfect Aire 1PAMSH36-MZO4-16 Installation Manual User Manual
Page 17
Fit the seal into the drain joint, then insert the
drain joint into the base pan hole of outdoor unit,
rotate 90 to securely assemble them.
Connecting the drain joint with an extension drain
hose (locally purchased), in case of the water
draining off the outdoor unit during the heating
mode.
Drain joint installation
Seal
Drain joint
Base pan hole of
outdoor unit
Seal
Drain pipe
Refrigerant pipe connection
Oblique
90
Roughness
Burr
Main cause for refrigerant leakage
is due to defect in the flaring work.
Carry out correct flaring work
using the following procedure:
A: Cut the pipes and the cable.
1. Use the piping kit accessory or pipes
purchased locally.
2. Measure the distance between the indoor
and the outdoor unit.
3. Cut the pipes a little longer than the
measured distance.
4. Cut the cable 59.1 inches (1.5m) longer than the pipe
length.
1. Flaring work
Fig.53
B: Burr removal
1. Completely remove all burrs from the cut
cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
Pipe
Reamer
Point down
Fig.54
Fig.55
C: Putting nut on
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal. (Not possible
to put them on after flaring work)
Flare nut
Copper tube
Fig.56
16
REFRIGERANT PIPE CONNECTION
(1)
(2)
NOTE: The drain joint differs from appliance
to appliance.
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A
"
Fig.57
D: Flaring work
Firmly hold copper pipe in a die in the
dimension shown in the table below.
Outer diam.
Inches (mm)
A (inches/mm)
Max.
Min.
1/4
6.35
0.052/1.3
0.03/0.7
3/8 (9.53)
0.062/1.6
0.04/1.0
0.04/1.0
1/2 (12.7)
0.071/1.8