Evacuating, Electrical connections, Power cable and connecting cable – Carrier XPOWER 38VYX110 User Manual

Page 11: Valve handling precautions

background image

38VYX110/38VYX130

GB - 10

All field electrical connections are the responsibility of the
installer.

WARNING:

• Wrong wiring may cause a burn-out to some electrical parts.

• Be sure to use the cord clamps attached to the product.

• Do not damage or scratch the conductive core and inner

insulator of power and inter-connecting cables when peeling
them.

• Be sure to comply with local regulations of the cable from

outdoor unit to indoor unit.
(wire size and cabling method etc.)

• Use the power and Inter-connecting cables with specified

thickness, specified type and protective devices required.

1. Connect the connecting cable to the terminal as identified with

their respective numbers on the terminal block of indoor and
outdoor unit.

• The indoor - outdoor unit interconnecting wires must be A07 RN-F

type (245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.

• The mains supply connecting cable for 38VYX units, must be H07 RN-F

type (245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.
Refer to the indoor unit installation manual for sizing of the
power supply wires.

2. For inter connecting cable, do not use a wire jointed to another

on the way.
Use wires long enough to cover the entire length.

Evacuating

• Open the valve stem or the handle until it strikes the stopper.

It is unnecessary to apply further force.

• Securely tighten the cap with a torque wrench.

• Cap tightening torque

Electrical connections

• Make refrigerant connections before electrical

connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.

IMPORTANT:
Make ground connection prior to any other electrical
connections.

Power cable and connecting cable

• The installation fuse (25A D type

) must be used for

the power supply line of this air conditioner.

• Incorrect/incomplete wiring might cause an electrical fire or

smoke.

• Prepare the exclusive power supply for the air conditioner.

• Ensure that mains supply connection is made through a

switch that disconnects all poles, with contact gap of a least 3
mm.

Connecting
cable

Power cable

Ground
connector

(mm)

10

30

1 2 3

10

10

L N

30

40

Terminal block power supply

Power cable

To the indoor unit

Earth

Connecting cable

Terminal block

Model

38VYX110

38VYX130

Power supply

220

÷

240 V

Single phase 50Hz

Maximum running current

22 A

22,8A

Installation

25 A (type D

)

fuse rating

Power cable

H07 RN-F (245 IEC 57)

2,5 mm

2

Size

ø 9,52

33 a 42 N•m (3,3 a 4,2 kgf•m)

ø 15,87

20 a 25 N•m (2,0 a 2,5 kgf•m)

Service connection

14 a 18 N•m (1,4 a 1,8 kgf•m)

Valve handling precautions

This manual is related to the following products: