Inspecting the Venting System

This appliance venting system was designed and con-
structed to develop a positive flow adequate to remove
flue gases to the outside atmosphere.
Any foreign object in the venting system, except those
designed specifically for the venting system, may cause
spillage of flue gases.
To inspect the venting system, make sure the main gas
valve is off. Remove glass frame (See Window Frame
Assembly Removal Section). Using a flashlight, check
the area above the baffle in the combustion dome.
Clean if necessary.

Test Chimney Draw

A "Chimney Draw" test must be made before the instal-
lation is complete.
1. Close all doors and windows in the home and start

exhaust fans in the kitchen and bathroom.

2. Light unit and operate for 5 minutes.
3. Hold an ignited match, cigarette or smoke match in

front of the unit. Refer to Figure 17 for location of the
draft hood opening.

4. Check to make sure smoke from the match, ciga-

rette or smoke match is drawn into the fireplace. If it

LO

HI

Turn

counterclockwise

to increase

flame height

Turn clockwise

to decrease

flame height

HV102

Honeywell hi/lo knob

4/5/99 djt

HV102

Fig. 13 Flame adjustment knob for Honeywell valve.

Turn

counterclockwise

to increase

flame height

Turn clockwise

to decrease

flame height

HV116

SIT 820 knob

1/14/02 djt

IH

LO

HV116

Fig. 14 Flame adjustment knob for SIT 820 valve.

F584-703

Honeywell

& PSE

pilot flames

3/8" - 1/2"

(10 - 13 mm)

SIT Pilot

PSE Pilot

F584-703

Fig. 15 Correct pilot flame appearance.

LG118

DV360

logs

1/26/00 djt

LG121

DV580

log flames

1/27/00 djt

Yellow Flame

Yellow

Flame

Red Glow

Red Glow

LG121

LG118

DV360

DV580

Fig. 16 Correct burner flame appearance.