Figure 33: Tilt Valve Calibration Screens

9. Select the Enter button (A) to begin calibration.

10. Follow the instructions on screens 1 – 3 then press the Enter button (B).

11. Follow instructions on screen 4 then press the Cal icon (C).

12. When the calibration is complete, press the Enter button (D) to exit calibration.

13. Table 2 shows examples of “before” and “after” calibration values. The new values should

be slightly higher to account for the additional UC5 wiring on the John Deere valve.

Table 2: Calibration Value Examples

Function Calibration

before

UC5

Installed

Calibration after UC5
Installed

Left Up

550

860

Left Down

600

910

Right Up

620

860

Right Down

620

900

14. Test Autofold and confirm that it is functioning properly. If it is not, repeat the calibration

procedure.