Microtel Series 1000 User Manual
Page 35

MICROTEL Series 1000 Dialer
29
z I/O Channel Type
*c2
Report I/O channel c TYPE
**c20n
Program I/O channel c TYPE
**c208Cv Program I/O channel c to Follow Channel C’s Value
Selection of I/O channel type (c = 1 to 8 for I/O channels starting at leftmost slot).
n Setting
Meaning
0
SPARE
No Type Selected
1
Digital Input Normally Open
Contact closure Normally Open
2
Digital Input Normally Closed
Contact closure Normally Closed
3
Digital Output
Digital Output that is user definable to
be Open or Closed
4
Analog Output (00.0 - 99.9%)
Analog Output that is user definable to
be at some setting
5
Analog Input (00.0 - 99.9%)
Current Percentage of an input value
6
Local Alarm Output
Digital Output that Closes when there
is a local alarm
8
Follow Channel Output
Digital Output that Closes depending
on the followed channel’s state
(see below)
Example- Command:
**3201
Response: Channel three type is one normally open digital input.
NOTE: When
using
Digital or Analog Outputs, see the section labeled Site
Control.
**c208CV Program I/O channel c to Follow Channel C’s Value
Value Setting
Meaning
C
Followed Channel (1-9)
The I/O Channel whose channel
status is being followed.
V
Type of Follow Channel (1-5)
0) Digital Output Follow Channel
1) Dout Follow Channel Status
2) Dout Follow Channel Alarm
3) Dout Follow Fill Algorithm
4) Dout Follow Empty Algorithm
The condition that this Output
Channel is following.
Example- Command:
**420832
Response:
Channel four type is eight digital output following channel three
alarm.
z I/O Alarm Configuration Selection of channel c’s alarm operation. For instance,
latched, call on alarm, etc.