2000 Fire Door-Fan Manual

updated 2002-05-28

Page 27 of 58

1.Turn ON the DM-1. Wait 30

seconds. Set first toggle to
“ZERO”

2. Press “Set to Zero” on DM-1

3. Set all toggles up. They should

be in the “Test, Room & Flow #1”
positions.

4. When this light is lit, all
connections have been made at

blower and it’s ready to go.
Turn on the power to blower #1.

5. Adjust the speed control to
get the required room pressure.

The blower must run at half
speed or more. If not change to a

lower (more restrictive) range.
Read the room pressure for 30

seconds.

6. When the desired room pressure
is achieved, flip the toggle up to

“Flow”. Read the flow pressure
(Flow #1) for 30 seconds. Turn the

blower OFF with the rocker switch
and turn the blower around to test

the other direction. Go to Step 3.