2000 Fire Door-Fan Manual

updated 2002-05-28

Page 22 of 58

Flow Range Diagram
Always start in the Flow Away position.

Adjust speed till room pressure is reached. Fan must be running at least at half speed and flow pressure must be
greater than room pressure. If not, insert the Range A plate and keep changing to lower ranges till motor is at

least half speed and flow pressure must be greater than room pressure.

Range 22 - Flow Away

Range A - Flow Away

Range B - Flow Away

Range C8 - Flow Away

Range C4 - Flow Away

Range C2 - Flow Away