beautypg.com

LAARS MAX 165 (DV) - Installation, Operation and Maintenance Instructions User Manual

Page 10

background image

Page 10

LAARS Heating Systems

particular conditions

3M. Indirect Hot Water Tank

Install the tank in accordance with the

manufacturers instructions using recommended pipe
sizes, location of temperature / pressure relief valve
and any other special requirement for correct
installation.

A thermal expansion tank may be required on

hot water tanks equipped with check valves or back
flow preventors on the cold water supply.

3N. Burner Controls

The burner is fitted with a fully automatic

control system which incorporates a cad cell to
monitor the flame and shut down the burner in the
event of flame failure. A push button is provided to
restart the burner, but this must never be pressed more
than once following a flame failure.

Pre-purge (direct vent only) provides an air

supply prior to oil flow to ensure clean combustion
under all conditions.

Post purge is also fitted to direct vent burners to

completely clear all residual gases from the boiler and flue
system. This is necessary with direct vent flues because of
the lack of draft prevailing after the burner shuts down. The
post purge time is factory set at 30 seconds.

3O. Fuel System (oil supply no heavier

than #2 fuel oil)

The oil supply should be run in heavy walled

copper tubing, without any joints, using flared fittings
only. It is important that the oil feed line to the burner
is air tight otherwise firing problems could result.

3P. Gravity Head System

Where the fuel supply is level with or above the

burner only a single pipe is required.

3Q. Suction Lift System

Where the burner is above the fuel supply a

return line must be provided in addition to the supply
line. The arrangement requires the fitting of the
bypass plug (provided) in the return port of the fuel
unit. Air is automatically purged from the fuel unit
and returned to the storage tank with this arrangement.

NOTE: If the suction lift exceeds 10 feet (3m),

a two stage fuel unit should be used. For Riello
burners obtain C700 kit for respective burners.

3R. Oil Filter

An in-line oil filter should be fitted in the supply

line and located inside the building between the tank
shut-off valve and as near to the burner as possible. A
shut-off valve should also be located close to the
burner for ease of servicing.

3S. Wiring

Wiring connections between burner and aquastat

on supply manifold should be made in accordance with
wiring diagrams in this manual (

see Figures 5 through

11

). External wiring must be in accordance with local

codes and regulations.

For convenience of servicing, a fuse disconnect

switch should be fitted near the boiler. Field
connections should be protected with a 15 amp fuse.

If an indirect hot water tank is used, the aquastat

on tank should be wired so as to have preference over
heating of the building. This requires the use of a
Honeywell L6006A-1145 or equivalent aquastat on
the tank working in conjunction with a zone valve or
circulator relay. See wiring diagrams in this manual.

On boilers piped direct (no zones) set anticipator

on thermostat to 0.8 amps.