Figure 8. Vent Terminal Clearance.
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
deck, or balcony
B= Clearance to window or door that may
Direct Vent Only: 12 inches (30 cm)
be opened
Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to side of opening; 1 foot (30 cm) above opening
C= Clearance to permanently closed window
See note 4
See note 5
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal
See note 4
See note 5
distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit
See note 4
See note 5
F= Clearance to outside corner
See note 4
See note 5
G= Clearance to inside corner
See note 4
See note 5
H= Clearance to each side of center line
See note 4
3 feet (91 cm) within a height 15 feet
extended above meter/regulator assembly
above the meter/regulator assembly
I= Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J= Clearance to nonmechanical air supply
Direct Vent Only: 12 inches (30 cm)
inlet to building or the combustion air inlet Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to any other appliance
to side of opening; 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)
6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location
Vent termination not allowed in this
driveway located on public property
location
M= Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.