beautypg.com

LAARS EDN Series - Installation, Operation and Maintenance Instructions User Manual

Page 17

background image

Endurance

Page 17

8. Connect boiler feed water supply with shut off

valve to inlet connection of automatic fill valve.

Locate in boiler outlet piping.

9. If codes require, install suitable back flow

preventer between automatic fill valve and city

main.

10. The appliance may be installed in single and

multiple zone systems (using either zone valves

or zone circulators) in the same manner as any

other residential boiler.

Caution

The EBP/EDP appliance must not be direct

connected to a heating system utilizing oxygen

permeable tubing (see warranty). Provide a water to

water heat exchanger between systems to prevent

corrosion of tank or other components. Non-toxic

heating system antifreeze may be added to the

hydronic system provided that the concentration

does not exceed 35% and the antifreeze contains

an anti foamant.

4.2 Use in a Combined Hot Water Heating

and Chilled Water Cooling System

When the appliance is used in connection with

a refrigeration system, it must be installed so that the

chilled medium is piped in parallel with the boiler with

appropriate valves to prevent the chilled medium from

entering it.

The boiler piping system of an appliance

connected to heating coils located in air handling

units where they may be exposed to refrigerated air

circulation must be equipped with flow control valves

or other automatic means to prevent gravity circulation

of the boiler water during the cooling cycle.

4.3 Water Quality and Treatment

Water quality control is steadily increasing in

importance in view of the use of modern regulation

technology and the modern boiler designs used in

central heating systems.

The life of a central heating boiler can be

severely diminished as a result of the formation

of scale deposits and/or corrosion products. The

formation of such deposits should be prevented

wherever possible.

Continual water make-up is not permitted.

A suitable water treatment may be used to

prevent excessive scale deposits in the boiler and

corrosion in the system.

4.4 Anti-Freeze

Proper precautions for freeze protection are

recommended for boiler installations in areas where

the danger of freezing exists.

4.4.1 Endurance Boiler Low

Temperature Feature

Endurance boilers are equipped with a Low

Temperature control feature that recognizes when the

water temperature at the outlet of the boiler has fallen

below 39°F (4°C). If this condition is recognized, the

Endurance pump will run for 5 minutes, or until the

boiler outlet temperature reaches 45°F (7°C). If the

boiler outlet temperature remains below 45°F (7°C)

for 5 minutes, the appliance will start its ignition

sequence, in hopes of firing the boiler and heating the

water. The display will show [ICE] during this time.

This feature is intended to assist in protecting

the boiler from freezing conditions, and does not help

to protect any other part of the heating system. This

feature will only help when there is power to the boiler

and when the internal water flow components in the

Endurance are working properly. This feature will

not be able to prevent freezing if the low temperature

water condition persists. See Section 4.4.2 for

information concerning further freeze protection for

the Endurance.

4.4.2 Anti-Freeze Boiler Additives

Caution

Power outage, interruption of gas supply, failure of

system components, activation of safety devices,

etc., may prevent a boiler from firing.

Any time a

boiler is subjected to freezing conditions, and

the boiler is not able to fire, and/or the water is

not able to circulate, there is a risk of freezing

in the boiler or in the pipes in the system. When

water freezes, it expands. This can result in bursting

of pipes in the system, or damage to the boiler,

which could result in leaking or flooding conditions.

Do not use automotive anti-freeze. When the

Endurance is the combination space heating domestic

water model (EBP), a non-toxic anti-freeze, such as

propylene glycol, must be used. Maintaining a mixture

of minimum 65% water and maximum 35% properly

inhibited HVAC glycol, which contains an anti-

foamant, is the preferred method of freeze protection

for Endurance boilers. Percentage of glycol used

in the Endurance boiler must not exceed 35%.

Typically, this mixture will serve as burst protection

for temperatures down to approximately -35°F (-30°C).

IMPORTANT NOTES: Different glycol products

may provide varying degrees of protection. Glycol

products must be maintained properly in a heating

system, or they may become ineffective. Consult the

glycol specifications, or the glycol manufacturer, for

information about specific products, maintenance

of solutions, and set up according to your particular

conditions.