beautypg.com

Flame sensor replacement procedure – LAARS U.H.E. - Service Manual User Manual

Page 33

background image

U.H.E Service Manual

Page 33

Flame Sensor Replacement Procedure

Step 4.

Fold back insulation in front of combustion assembly to expose flame sensor.

(see photo at right)

Step 5.

Disconnect wire lead from flame sensor.

Step 6.

Remove the 2 sensor mounting screws (magnetic

tip, long reach Phillips screw driver) and remove

flame sensor & gasket from transition base

flange.

Step 7.

Remove any residual gasket material from

transition base flange.

Step 9.

Reconnect flame sensor wire.

Step 10.

Fold insulation back into place. Be sure no wires are in

contact with burner flange.

Step 8.

Install new flame sensor with new gasket provided

using screws from step 6. Arrange flame sensor with

hook towards burner.

Step 1.

Position main power switch to “OFF”

Step 2.

Disconnect (unplug) water heater

from 120 volt power source.

Step 3.

Un-latch & remove surround cover

from top of heater.

Step 11. Restore 120 volt power supply to water heater and confirm proper operation following the

lighting instructions on the lighting instruction label or the lighting instructions located in

the installation and operating instruction manual.

Step 12. Replace surround cover on top of

water heater.

Transition

base flange

Flame sensor

mounting screws

Flame sensor

Flame sensor

gasket

Arrange hook

of sensor

towards burner

Flame

sensor

WARNING

120 volt potential exposure. Isolate the

appliance and reconfirm power is

disconnected using a multi-meter.

33