Page 18

background image

LAARS Heating Systems

Page 18

Does inlet gas pressure

drop more than 2" W.C.

during burner ignition?

Adjust gas

supply regulator

Inadequately

sized regulator.

Y

N

N

Y

N

Y

N

IGNITION MODULE

Verify Minimum Gas Supply Piping Requirements of:

Minimum 1" NPT for UHE100T399, all others use ¾"

NPT. (Schedule 40 black Iron Pipe recommended).

Reconfigure gas

supply piping

Y

Observe burner operation through the sight glass located on the combustion insert mounting flange. Normal burner operation

should ignite smoothly, without evidence of coughing or huffing upon ignition. The burner flame should be a blue flame near the

burner surface in a uniform flame pattern. Occasional yellow or white streaks are normal.

Inlet gas

pressure tap

Venturi

adjustment

Is igniter resistance

less than 150 Ohms

(cold)?

(see check igniter

illustration)

Refer to ignition module illustration below,

is there 120VAC across terminals

P6(1) and P6(2)?

(Note: Igniter LED must be lit during this check).

Y

N

Replace

hot surface igniter.

(see page 30)

Replace ignition module.

(see page 34)

N

Y

Do you see the igniter

glowing through burner

site glass during the

warm up period?

Proceed to next page

With manometer, check inlet

gas pressure. Is it stable

between 7" & 14" W.C. static?

(heater not running)

(see illustrations at right)

Is gas supply pressure

regulator adjustable to

maintain proper and

stable setting?

Y

N

Volt meter set to

OHM setting

Meter probe

Hot surface

igniter

CHECK IGNITER

RESISTANCE

WARNING

120 volt potential

exposure. Use caution

making voltage checks to

avoid personal injury.

WARNING

Removing screw from

inlet gas pressure tap will

immediately allow gas to

flow from pressure tap.

Note: On higher input models using metal fiber mesh burner (serial

number “CK” and later) a red glow from the burner surface is normal.

18