beautypg.com

LAARS U.H.E. - Installation Manual User Manual

Page 19

background image

Figure 12a. Vent Terminal Clearances (Other than Direct Vent or “Power Vented” Installations)

Canadian

Installations

1

US Installations

2

Canadian

Installations

1

US Installations

2

A= Clearance

above

grade, veranda,
porch, deck or
balcony

12 inches

(30 cm)

12 inches

(30 cm)

H=

Clearance to each side
of center line extended
above meter/regulator
assembly

3 feet (91 cm) within a

height 15 feet (4.6 m)

above the

meter/regulator

assembly

*b

B= Clearance

to

widow

or door that may be
opened

36 inches

(91 cm)

4 feet (1.2 m)

below or to the

side of opening;

12 inches (30

cm) above

opening

I=

Clearance to service
regulator vent outlet or
oil tank vent

36 inches

(91 cm)

*b

C= Clearance

to

permanently closed
widow

*b

*b

J=

Clearance to non-
mechanical air supply
inlet to building or the
combustion air inlet to
any other appliance

36 inches

(91 cm)

4 feet (1.2m)

below or to side

of opening; 12

inches (30 cm)

above opening.

D= Vertical clearance to

ventilated soffit
located above the
terminal within a
horizontal distance of
2 feet (61 cm) from
the center line of the
terminal

*b

*b

K=

Clearance to a
mechanical air supply
inlet

6 feet

(1.83 m)

3 feet (91 cm)

above if within

10 feet

horizontally

E= Clearance

to

unventilated soffit

*b

*b

L=

Clearance above paved
sidewalk or paved
driveway located on
public property

7 feet

(2.13 m)†

7 feet

(2.13 m)†

F=

Clearance to outside
corner

*b *b

M=

Clearance

under

a

veranda, porch, deck, or
balcony

12 inches (30 cm) ‡

*b

G= Clearance to inside

corner

36 inches
(91 cm)*a

36 inches
(91 cm)*a

1

In accordance with the current CAN/CGA-B149 Installation Codes.

2

In accordance with the current ANSI Z223.1-(Latest Edition)/NFPA 54 National Fuel Gas Code.

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family

dwellings and serves both dwellings.

Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.

*a) A minimum clearance value determined by testing in accordance with section 2.20.
*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.

19