beautypg.com

LAARS Mighty Therm HH-PH (Sizes 175-400) - Installation, Operation and Maintenance Instructions User Manual

Page 15

background image

Mighty Therm HH-PH Hydronic Boilers

Page 15

2F-6. Chilled Water Systems
If the boiler is part of a refrigeration system,

include the right valves to isolate the boiler from the

refrigeration system during times when the boiler is

not operating.

When the boiler piping is connected to heating

coils, which are close to refrigerated air circulation,

install flow control valves or other automatic methods

to prevent gravity circulation of the boiler water

during the cooling cycle.

2F-7. System to Boiler Piping

1.

Install gate valves at the inlet and outlet to the

boiler so it can be isolated for service.

2.

Make sure the pressure relief valve (see Figure

26) has its outlet piped to a drain or floor sink.

Pay special attention to relief valve settings in

installations where the boiler is located on the

ground floor of a tall building, or where the

operating temperature of the boiler is above

210°F (99°C). In both cases, the static pressure

of the system is raised. This would bring raw

water into the system. The factory will furnish a

75 psi (516.8 kPa) setting unless a special setting

is ordered.

3.

Install a low water cutoff device if the boiler is

installed above radiation level.

4.

Install manual and/or automatic air venting

devices at high points in the system to get rid

of air.

5.

Install a correctly sized expansion or

compression tank in accordance with the

manufacturer's instructions.

6.

Support the weight of all water and gas piping

with suitable hangers or floor stands.

7.

Check piping diagrams with local applicable

plumbing, heating and building safety codes.

2F-8. Filling the System

1.

Close all air vents and open the makeup water

valve. Let the system fill slowly.

2.

If a makeup water pump is used, adjust the

pressure switch on the pumping system to

maintain at least 12 psi (82.7 kPa) at the highest

point in the heating loop.

3.

If a water pressure regulator is installed on the

makeup water line, adjust the pressure regulator

to provide at least 12 psi (82.7 kPa) at the

highest point in the heating loop.

4.

Open air vents on all radiation units at the high

points in the piping throughout the system,

unless automatic air vents are installed at those

points.

5.

Run the system circulating pump for at least 30

minutes with the boiler shut off.

6.

Recheck all air vents as described in Step 4 above.

7.

With the system full of water and under normal

operating pressure, the air pressure in the expansion

tank should be at least 12 psi (82.7 kPa).

8.

Start up the boiler following the instructions

found on the inside of the boiler.

9.

Operate the whole system, including the pump,

boiler, and radiation units for 1 hour.

10. Shut down the entire system and vent all

radiation units and high points in the system

piping as described in Step 4 above.

11. Close the makeup water valve and check the

strainer in the pressure reducing valve for sedi-

ment or debris. Reopen the makeup water valve.

12. Check the gauge to make sure the water pressure

is right, and check water level in the system. If

the water level indicated above the boiler shows

that water is at the highest point in the circulating

loop, then the system is ready for operation.

13. Within 3 days of start-up, recheck all air vents

and expansion tank as described in Steps 4 and 8

above.

2F-9. Minimum Boiler Temperature
The boiler inlet water temperature must be

minimum 110°F (43°C) when the system has come up

to normal operating conditions. Lower temperature

inlet water may allow the production of condensation

on the outside of the copper finned tubes, which can

block the flue gases and/or cause improper

combustion, leading to heat exchanger sooting.

For systems with lower than 110°F (43°C)

temperature, boiler must be protected from low

temperature return water. There are many methods of

achieving low temperature protection. Figures 22 and

25 shows an example of such a system.

FLOW
SWITCH

PRESSURE
RELIEF
VALVE

HIGH-LIMIT
DRY WELL

Figure 26. Pressure Relief Valve.