Page 44

WARNING

Failure to rinse the debris from the heat exchanger

and temporary drain line may lead to clogged

condensate lines, traps and neutralizers. Condensate

pumps (if used) may also be damaged from the

debris left behind, possibly causing property damage.

10. Install all components removed in the reverse

order to place the appliance back in operation.

Make sure all gaskets are in place as components

are installed. Replace any damaged gaskets. Do

NOT reuse damaged gaskets.

11. Place the appliance in operation according to

Section 10

checking all gas connections for leaks.

Confirm all fasteners are tight.

11.2.7 Gas Conversion

There are no parts or orifices required for the gas

conversion of the Mascot LX. But if a gas conversion

is performed, the unit must be identified with the

appropriate gas labels and a conversion sticker to allow

technicians performing maintenance in the future to

properly identify the gas type of the appliance. These

stickers are included with the boiler during shipment.

Conversion to/from LP Gas Instructions:

1. Open the front covers as described in Section 1

and

Figure 1

.

2 Place "Propane Gas" sticker over the "Natural

Gas" sticker (or vice versa) where the gas supply

line enters the appliance.

3. Fill out gas conversion sticker with all of the

required information and place adjacent to the

Rating Plate sticker (which is behind the center

door panel).

4. Confirm that the gas supply is turned on.
5. Start boiler per lighting procedure shown on inside

front cover or side of appliance.

6. With a combustion analyzer, check CO2 levels at

both maximum and minimum input.

Refer to sections

Figure 26

and

Table 17

of this

manual for the proper adjusting procedures.

7. Close all front covers.

WARNING

Serious injury or death could occur if CO

2

levels are

not adjusted properly.

__________________________________________

NATURAL

NATUREL

H0011700

F

1.0"

3.0"

WARNING

This conversion shall be installed by a qualified

service agency in accordance with the manufacturer's

instructions and all applicable codes and

requirements of the authority having jurisdiction. If

the information in these instructions is not followed

exactly, a fire, an explosion or production of carbon

monoxide may result causing property damage,

personal injury or loss of life. The

qualified service agency is responsible

for the proper and complete installation

of this kit. The installation is not proper

and complete until the operation of the

converted appliance is checked as specified in the

manufacturer's instruction supplied with the kit.

AVERTISSEMENT

Ce conversion doit être installé par un organisme de

service conformément aux instructions du fabricant

et tous les codes et les exigences de l'autorité

compétente. Si les informations contenues dans ces

instructions n'est pas suivi à la lettre, un incendie,

une explosion ou de la production de monoxyde

de carbone mais résultat causant des dommages

matériels, des blessures ou des pertes de vie. Le

service est responsable pour la bonne et complète

l'installation de ce kit. L'installation n'est pas correcte

et complète jusqu'à ce que le fonctionnement de

l'appareil converti est vérifiée comme spécifié dans le

manuel d'instruction fourni avec le kit.

Figure 27. Natural Gas Sticker

Figure 28. Propane Gas Sticker


This boiler has been converted to use:

3.50"

2.00"

20 Industrial Way

Rochester, NH 03867

H2200500D

Converted
by:

Date:

Natural Gas

Propane