Page 27

SECTION 7.

Electrical Connections

WARNING

The appliance must be electrically grounded in

accordance with the requirements of the authority having

jurisdiction or, in the absence of such requirements, with

the latest edition of the National Electrical Code, ANSI/

NFPA 70, in the U.S. and with latest edition of CSA

C22.1 Canadian Electrical Code, Part 1, in Canada. Do

not rely on the gas or water piping to ground the metal

parts of the boiler. Plastic pipe or dielectric unions may

isolate the boiler electrically. Service and maintenance

personnel, who work on or around the boiler, may be

standing on wet floors and could be electrocuted by an

ungrounded boiler. Electrocution can result in severe

injury or death.

Single pole switches, including those of safety controls

and protective devices must not be wired in a grounded

line.
All electrical connections are made on the terminal

blocks that are located inside the control panel.

NOTE: All internal electrical components have been

prewired. No attempt should be made to connect

electrical wires to any other location except the terminal

blocks.

CAUTION

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing

CAUTION

Mascot LX supply voltage must not be disengaged,

except for service or isolation, or unless otherwise

instructed by procedures outlined in this manual. To

signal a call for heat, use the 24V DC field-interlock,

as shown in the wiring diagram(s).

7.1 Main Power

Plug power cord into a non-switched 115V electrical

outlet with 15A circuit protection. FLA is 2A. There

is an internal 10A breaker to protect internal system

components.

7.2 Pump Connections

Mascot LXC energizes boiler pump (opens 3-way

valve), and system pump upon a demand for Central

Heat. Mascot LXH energizes boiler pump and system

pump upon a central heat demand

The combined load for all pumps must not exceed

5 amps. In some installations, a pump relay may be

required.

7.3 24Vac Transformer with Circuit Breaker

24Vac is supplied by a transformer mounted behind the

lower door. All 24Vac power is supplied through a 2A

circuit breaker located behind lower door.

7.4 Central Heat - Call for Heat

Connect the Call for Heat to terminals #5 and #6

(connections labeled "T-T or interlock").

7.5 Outdoor Air Temperature Sensor

Connect the outdoor air temperature sensor to

connections labeled "Outdoor sensor." The outdoor air

temperature sensor is used for warm weather shutdown

and outdoor reset. If an outdoor sensor is not installed,

the CH setpoint of the boiler is limited to 140°F.

7.6 Domestic Hot Water Connection

For indirect water heater, connect aquastat for remote

sensor to terminals #7 & #8 or domestic hot water

sensor to terminals #9 & #10 (see

Figure 21

).

Domestic Hot Water Sensor PN is E2337501

7.7 System Sensor

Connect the system sensor to connections labeled

"system sensor" on lead boiler only. #3 and #4

7.8 External Control Connections

If the unit is being controlled by an external 0-10VDC

signal, connect this to terminals 11 and 12. When

making the connections, follow the polarity designations

shown on the label. A "dry" alarm contact is located on

terminals 10 and 11 at high voltage panel (backside).
Note: The 0-10VDC signal may be to send a modulation

signal, or a temperature setpoint signal to the boilers

from a building management program (See Section 9).