CAUTION
Condensate is mildly acidic (pH=5), and may harm some floor drains and/or pipes, particularly those that are
metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand
the acidity, or neutralize the condensate before disposal.
Damage caused by failure to install a neutralizer kit
or to adequately treat condensate will not be the manufacturer’s responsibility.
Contact Laars to order Kit# A2123601
__________________________________________________________________________________________
Figure 13. DHW Connections with Anti-Scald Valve
and Flow Restrictor.
6.7 Condensate Drain
A condensate drain trap is built into the Mascot LX.
Connect a 3/4” PVC pipe between the drain connection
and a condensate neutralizer before entering drainage
system.
The condensate drain and included trap must be
installed. When a condensate pump is not used, the
tubing must continuously slope downward toward the
drain with no spiraling.
Consult local codes for the disposal method.
- Mascot LX MLXC 150 MBH - Install and Operating Manual Mascot LX MLXC 125 MBH - Install and Operating Manual Mascot LX MLXH 220 MBH - Install and Operating Manual Mascot LX MLXH 175 MBH - Install and Operating Manual Mascot LX MLXH 150 MBH - Install and Operating Manual Mascot LX MLXH 125 MBH - Install and Operating Manual Mascot LX MLXH 100 MBH - Install and Operating Manual Mascot LX MLXH 75 MBH - Install and Operating Manual Mascot LX MLXH 50 MBH - Install and Operating Manual