LC-202P/LC-208P
Quick Start Guide
5.4.2
LC-208P/LC-208P Combination
Perform the following wiring instructions to accommodate an elevator application using two LC-
208P panels; up to 16 floors (for 32 floors, add a third LC-208P and continue the daisy-chain wiring
to the third panel).
1. Make a complete set of connections to the first LC-208P panel. Refer to Section 5.3 on page 14
for all connections to the LC-208P. This panel must have the master elevator controller (the
controller with address 1).
2. Daisy-chain the Antenna and Ground reader connections from the terminal strip on the first
panel to the terminal strip on the second panel. Make the connections per the information in
Table 8 and Figure 12.
Figure 12: LC-208P to LC-208P Wiring Connections
Table 8: LC-208P to LC-208P
First LC-208P Reader
Terminal Strip
Second LC-208P Reader
Terminal Strip
Reader Antenna
Reader Antenna
Reader Ground
Reader Ground