Quick Start Guide
LC-202P/LC-208P
Figure 5: Floor Control Relay Connection
5.2.2
RS-485 Controller Network
All of the controllers in the elevator network communicate through an RS-485 serial
communication network. Per the RS-485 industry specification, this network must be daisy-
chained, with a total network cable length of no more than 4,000 feet. Make the RS-485 network
connections per the information in Table 3 and Figure 6 on page 11.
NOTE: Do NOT connect earth ground to the RS-485 network cable shield. The LC-200P controller
automatically connects earth ground to the shield at one point on the network. This single
connection minimizes the effects of ground loops that can affect controller performance.
Table 3: RS-485 Controller
Network
TB-1 Pin
Description
1
Tx/Rx Negative
2
Tx/Rx Positive
3
Network Cable Shield