2 lc-508w/lc-508w combination, Wiegand elevator control panel – Keri Systems LC-508 Wiegand Elevator Control User Manual
Page 21
Wiegand Elevator Control Panel
2305 Bering Drive
01942-001 Rev. D
San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]
Page 21 of 24
LC-502W/LC-508W
Quick S
tart Guide
5.4.2
LC-508W/LC-508W Combination
Perform the following wiring instructions to accommodate an elevator application using up to four
LC-508W panels (up to 32 floors).
1. Make a complete set of connections to the first LC-508W panel. Refer to Section 5.3 on page 16
for all connections to the LC-508W.
2. Daisy-chain the Data0, Ground, and Data1 reader connections from W-TB-B of the additional
LC-508W panel to W-TB-C of the previous LC-508W panel. Make the connections per the
information in Table 9 and Figure 14 on page 22.
3. Daisy-chain the TxRx+, TxRx-, and Shield Network Communication connections from W-TB-
B of the additional LC-508W panel to W-TB-C of the previous LC-508W panel. Make the
connections per the information in Table 10 and Figure 15 on page 23.
4. The floor/relay connections for the additional LC-508W are made according to the floor/panel
association. Refer to Section 5.3 on page 16 for all floor/relay connections to the LC-508W.
Power connections are made per the instructions in Section 5.2.4 on page 16.
Table 9: LC-508W to LC-508W Panel Wiring Connections
W-TB-B
W-TB-B of Additional
Panel
W-TB-C of First/Previous
Panel
W-TB-C
Pin 1
Reader Ground (OUT)
Reader Ground (IN)
Pin 13
Pin 2
Data0 (OUT)
Data0 (IN)
Pin 16
Pin 3
Data1 (OUT)
Data1 (IN)
Pin 10
Table 10: LC-508W to LC-508W Panel Network Communication Wiring
W-TB-B
W-TB-B of Additional
Panel
W-TB-C of First/Previous
Panel
W-TB-C
Pin 4
TxRx - (OUT)
TxRx - (IN)
Pin 1
Pin 5
TxRx + (OUT)
TxRx + (IN)
Pin 2
Pin 6
Shield (OUT)
Shield (IN)
Pin 3