4 wiring multiple panels together, 1 lc-508w/lc-502w combination, Wiegand elevator control panel – Keri Systems LC-508 Wiegand Elevator Control User Manual
Page 18

Wiegand Elevator Control Panel
2305 Bering Drive
01942-001 Rev. D
San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]
Page 18 of 24
Quick S
tart Guide
LC-502W/LC-508W
5.4
Wiring Multiple Panels Together
Up to 32 floors can be controlled using LC-508Ws.
5.4.1
LC-508W/LC-502W Combination
Perform the following wiring instructions to accommodate an elevator application using an LC-
508W and one or more LC-502W panels.
1. Make a complete set of connections to the LC-508W panel. Refer to Section 5.3 on page 16 for
all connections to the LC-508W.
2. Daisy-chain the Wiegand Data0, Ground, and Data1 reader connections from W-TB-B to the
LC-502W panels. Make the connections per the information in Table 7 and Figure 12 on
page 19.
3. Daisy-chain the RS-485 TxRx+, TxRx-, and Shield network communication connections from
the W-TB-B terminal strip on the LC-508W to each of the LC-502W panels. Make the
connections per the information in Table 8 and Figure 13 on page 20.
4. Refer to Section 5.2.4 on page 16 for the LC-502W panel power connections.
5. Refer to Section 5.2.1 on page 10 for the LC-502W floor relay connections.
Table 7: LC-508W W-TB-B to LC-502W Panel
W-TB-B
Connection
LC-502W TB-5/TB-6
Pin 1
Reader Common
Pin 4
Pin 2
Data0
Pin 1
Pin 3
Data1
Pin 7
Table 8: LC-508W to LC-502W Panel
RS-485 Network Communication Wiring
W-TB-B
Connection
LC-502W TB-1
Pin 4
TxRx-
Pin 1
Pin 5
TxRx+
Pin 2
Pin 6
Shield
Pin 3