Wiegand Elevator Control Panel

2305 Bering Drive

01942-001 Rev. D

San Jose, CA 95131 USA
(800) 260-5265 (408) 435-8400 FAX (408) 577-1792
Web: www.kerisys.com E-mail: [email protected]

Page 13 of 24

LC-502W/LC-508W

Quick S

tart Guide

5.2.3

Reader/Amplifier Daisy-Chain

One Wiegand reader is shared by all elevator control panels in an elevator control application. The
Wiegand reader connections are made to the master LC-502W elevator panel, through a Wiegand
Distribution Amplifier (P/N 04197-001 – see Figure 8).

Figure 8: Wiegand Distribution Amplifier

Make the Wiegand reader to Distribution Amplifier connections per the information in Table 3
and Figure 9 on page 15.

Make the Distribution Amplifier to master elevator panel connections per the information in
Table 4 and Figure 9 on page 15.

Table 3: Wiegand Reader to Distribution

Amplifier

Reader

Amplifier WDA-TB-1

Data0

Pin 1

Beeper

Pin 2

Power

Pin 3

Ground and Cable Shield

Pin 4

Green LED (Dual)

Pin 5

Red LED (Single)

Pin 6

Data1

Pin 7