Install HGBP/Pump Board and Control Wiring

1. Attach the solenoid coil assembly to the solenoid valve

plunger on the tube assembly for each circuit. One cable

assembly TH70400410 is supplied per circuit. Secure the

DIN connector end on the solenoid valve coil with the

screw in the connector. Verify the square rubber gasket is

in place to ensure connection remains watertight.

2. Route the other end of the cable to the main control panel

(where the display is located). For the circuit A solenoid,

connect leads to TB5-7 and TB5-13. For the B circuit

solenoid, connect leads to TB5-8 and TB5-13. For the C

circuit solenoid (30XA400-500 only), connect the leads

to TB5-6 and TB5-13. In all cases, the black wire from

the solenoid must be connected to TB5-13 to ensure

correct polarity.

3. Set the board address of the HGBP/Pump Board by posi-

tioning the dual in-line package (DIP) switches to the

correct settings. See Fig. 5. Mount the HGBP/Pump board

in the main control panel with the No. 8 screws provided

(mounting standoffs required for 30XA080-120: 200 v,

230 v, 380 v and 30XA140-500: all voltages). See Fig. 6A

and 6B for the board mounting location.

4. Mount the 24-v circuit breaker (CB14) in the CB14

mounting hole on the display bracket. See Fig. 6A and 6B

for the mounting hole location.

5. Connect the 24-v power from TB10-X1 (30XA080-120:

460 v, 575 v only) or TB11-X1 (30XA080-120: 200/230 v

and 30XA140-500: all voltages) to CB14 with the

provided red wire in the harness assembly. Find two 2-pin

plugs marked J1-11,12 with red and brown wires in the

harness assembly. Connect the plug to the HGBP/Pump

board J1 with the red wire connected to CB14 and the

brown wire connected to TB10-X2 (30XA080-120: 460 v,

575 v only) or TB11-X2 (30XA080-120: 200/230 v and

30XA140-500: all voltages). See Fig. 7.

6. Using harness TH70400864 provided in the kit, connect

TB5 pins 6 (30XA400-500 only), 7, 8, and 13 to HGBP/

Pump board J2 CH3, CH4 and J3 CH5 (30XA400-500

only). Use the pins inside TB5. See Fig. 5.

7. For 30XA080-120: 200/230 v, 380 v and 30XA140-500:

all voltages, disconnect the 3 pin plug on MBB J9B (or

EMM board J9A) for communication and plug it in to the

HGBP/Pump board J9. Use the additional communica-

tion cable assembly TH70400852 provided in the kit to

connect between HGBP/Pump board J9 and MBB J9B

(or EMM board J9A when EMM board exists). The com-

munication cable in the TH70400864 harness will not be

used. For 30XA080-120: 460 v, 575 v, connect the 3 pin

plug of the communication cable in the TH70400864

harness to the HGBP/Pump board J9 and splice the other

end of the cable to the communication network using the

wire nuts provided in the kit. Be sure to splice the wires

with same color together to ensure correct polarity.

Take care connecting leads to terminal blocks. Incorrect

polarity will damage the control boards.

a30-4503

Fig. 5 — HGBP/Pump Board Address Switch and

Wiring for Minimum Load Solenoid Output

HGBP/PUMP

BOARD

CB14

Fig. 6A — HGBP/Pump Board and CB14 Mounting Location

(30XA080-120: 200 v, 230 v, 380 v and 30XA140-500: all voltages)

a30-4504