Mounting the touchpad, Setting touchpad unit numbers, Power up and bus communication – Interlogix SuperBus 2000 2X20 User Manual
Page 4: First touchpad

Figure 5: Wiring the touchpad to Ultragard panels
12
13
14
15
GND
DC
OUT
BUS
B
BUS
A
CONTROL PANEL
NOT
USED
OPTIONAL
SWITCH
WITH MAGNET
YELLOW
BLACK
RED
WHITE
GREEN
WIRING HARNESS
49-430
TAB
SLOT (3)
(Not to be used in UL
listed installations)
SHIELDED
CABLE
C onnect Shield To Earth Ground
Mounting the Touchpad
1. Align the slots on the touchpad with the slots on the back-
plate. Insert the mounting tabs into the mounting slots and
press the keypad toward the wall/gang box.
2. Tighten the two bottom screws.
Setting Touchpad Unit Numbers
Note: In multiple partition systems all new touchpads default to
partition 1. To change partition assignment please see specific
panel Installation Instructions. All partitions must be disarmed
before entering program mode.
Panels automatically assign or learn the unit numbers of each
bus device upon power up or entering programming mode.
SuperBus 2000 panels (Advent panels and Concord panels
with software version 2.0 or newer) automatically assign
different unit numbers to each SuperBus 2000 module.
SuperBus panels (UltraGard panels and Concord panels with
software versions 1.0–1.6) do not automatically assign different
unit numbers to each SuperBus 2000 module. For these
panels, alphanumeric touchpads default to 001. If desired or
necessary, the unit number must be manually changed.
Guidelines for Assigning Alphanumeric Touchpad
Unit Numbers (Concord panels with software
versions 1.0–1.6 and UltraGard panels)
Use the following guidelines to avoid communication conflicts
between bus devices and the panel:
•
Always start with one touchpad connected to the panel
and make sure it is working properly before connecting
additional touchpads.
•
Whenever possible, such as in new installations, assign
alphanumeric touchpad unit numbers before beginning all
other panel programming.
•
Other bus devices with device unit number DIP switches
(ESM, HIM, etc.) must be set to the desired unit number
before applying power and entering program mode.
Power Up and Bus Communication
Powering up Concord Panels with Software Version
2.0 or Newer and Concord Express/Concord Ultra
Panels
1. Verify that all wiring between the panel and touchpad is
correct.
2. Connect the panel battery and plug in the panel
transformer. Alphanumeric touchpads show “SCANNING
BUS DEVICES,” then a date and time display.
3. Verify correct operation by pressing *. The display should
show the current system status.
Note: If after pressing * the touchpad does not display the
current system status, see “Troubleshooting.”
Powering up Concord Panels with Software Versions
1.0–1.6
First Touchpad
1. Verify that all wiring between the panel and touchpad is
correct.
2. Check the unit number DIP switches on all other bus
devices (ESM, HIM, etc.) and make note of their
respective unit numbers.
Note: Touchpads default to unit number 001 when first
installed. If possible, leave this unit number open. If unit
number 001 is not available, or there are multiple
touchpads installed see the section “Additional
Touchpads” below.
3. Connect the panel battery and plug in the panel
transformer. Alphanumeric touchpads show “SCANNING
BUS DEVICES,” then a date and time display.
4. Verify correct operation by pressing *. The display should
show the current system status.
Note: If after pressing
*
the touchpad does not display the
current system status, see “Troubleshooting” on page 7.
4
SuperBus 2000 2X20 LCD Alphanumeric Touchpad Installation Instructions