Fresh air for combustion and ventilation, Warning – Desa Tech CGN20T User Manual

Page 7

background image

7

103873

FRESH AIR

FOR

COMBUSTION

AND

VENTILATION

Continued

WARNING ICON

G 001

WARNING

If the area in which the heater may be operated is smaller than that
defined as an unconfined space, provide adequate combustion and
ventilation air by one of the methods described in the

National Fuel

Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to
an adjoining unconfined space, you must provide two permanent openings: one
within 12" of the ceiling and one within 12" of the floor on the wall connecting the
two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining
room (see option 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI
Z223.1, Section 5.3, Air for Combustion and Ventilation
for required size of ventila-
tion grills or ducts.

WARNING ICON

G 001

WARNING

Rework worksheet, adding the space of the adjoining unconfined
space. The combined spaces must have enough fresh air to supply all
appliances in both spaces.

Figure 2 - Ventilation Air from Inside Building

Continued

Or

Remove

Door into

Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1