Ari* capacities, Cooling capacities and efficiencies, A--weighted sound power (dba) – Carrier 50XP User Manual
Page 4: 50x p

4
ARI* CAPACITIES
Cooling Capacities and Efficiencies
UNIT 50XP
NOMINAL TONS
STANDARD CFM
NET COOLING
CAPACITIES (Btuh)
EER**
SEER†
024
2
770
24,000
11.0
13.2
030
2--1/2
960
29,000
11.0
13.0
036
3
1100
36,000
11.2
13.5
042
3--1/2
1450
41,000
11.2
13.0
048
4
1450
45,000
11.0
13.0
060
5
1710
57,000
11.0
13.0
LEGEND
dB---Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning & Refrigeration Institute.
**At “A” conditions---80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F (35_C) outdoor db.
{
Rated in accordance with U.S. Government DOE Department of Energy)
test procedures and/or ARI Standards 210/240.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7_C) db, 67°F wb (19.4_C) indoor entering---air
temperature and 95°F db (35_C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and effi-
ciency information available from your retailer.
A--Weighted Sound Power (dBA)
50XP
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
125
250
500
1000
2000
4000
8000
024
72
58.8
63.5
67.2
66.9
63.7
58.3
50.0
030
72
58.8
63.5
67.2
66.9
63.7
58.3
50.0
036
72
60.7
63.3
66.8
66.5
64.2
60.3
53.0
042
72
56.7
62.8
67.8
67.4
63.7
57.7
50.8
048
78
62.4
69.9
71.3
73.4
70.0
66.3
60.1
060
78
63.5
67.6
71.8
75.5
71.0
68.1
59.9
* Tested in accordance with ARI Standard 270 (not listed in ARI).
50X
P