Selection procedure, 50xp unit suggested rigging, Selection procedure (with example) – Carrier 50XP User Manual
Page 11: Select unit based on required cooling capacity, Select electric heat

11
50XP UNIT SUGGESTED RIGGING
1
2
3
4
A07216
DETAIL A
(914 mm)
A08005
Unit*
SMALL CABINET
LARGE CABINET
024
024
030
030
036
036
Unit*
042
042
048
048
060
060
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
Rigging
Weight
345
156
349
158
367
166
Rigging
Weight
425
193
459
208
504
229
NOTE: See dimensional drawing for corner weight distribution. Corner weights shown on drawing are based on unit---only weights and do not include pack-
aging.
SELECTION PROCEDURE (WITH EXAMPLE)
1. Determine cooling and heating requirements at
design conditions:
Given:
Required Cooling Capacity (TC)
34,500 Btuh
. . . . . . . . . .
Sensible Heat Capacity (SHC)
26,000 Btuh
. . . . . . . . . . . .
Required Heating Capacity
15,000 Btuh
. . . . . . . . . . . . . . .
Condenser Entering Air Temperature
95°F(35°C)
. . . . . . . .
Indoor--Air Temperature
80°F (26°C) edb
. . . . . . . . . . . . .
67°F (19°C) ewb
Evaporator Air Quantity
1200 CFM
. . . . . . . . . . . . . . . . . .
External Static Pressure
0.20 IN. W.C.
. . . . . . . . . . . . . . . . .
Electrical Characteristics
230--1--60
. . . . . . . . . . . . . . . . . . .
2. Select unit based on required cooling capacity.
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F (35°C). The 036 unit at 1225 CFM and 67°F
(19°C) ewb (entering wet bulb) will provide a total capacity of
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
3. Select electric heat.
The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.
15,000 Btuh
= 4.4kW of heat required
3,414 Btuh/kW
Enter the Electric Heater Packages table for 208/240, single--phase,
036 unit. The 5 kW heater at 240v most closely satisfies the
heating required. To calculate kW at the 208v, multiply the heater
kW by multiplication factor 0.75 found in the Wattage
Multiplication Factors table.
5 kW x 0.75 = 3.75 kW
3.75 kW x 3414 = 12,802.50 Btuh
4. Determine fan speed and power requirements at
design conditions.
Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Filter Pressure
Drop Table, and the Accessory Electric Heat Pressure Drop table,
find:
External Static Pressure
0.200 IN. W.C.
Filter
0.130 IN. W.C.
Wet Coil Pressure Drop
0.032 IN. W.C.
Total Static Pressure
0.362 IN. W.C.
Enter the table for Dry Coil Air Delivery—At 0.362 IN. W.C. ESP
(external static pressure) and NOM speed pin selection, the motor
will deliver 1235 cfm.
5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208--1--60.
50X
P