Acquire the switch on the infinet network – Crestron electronic CLW-SW1/4RF User Manual
Page 12

infiNET™ Switches
Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF
Acquire the Switch on the infiNET Network
Before an infiNET device can be used on an infiNET network, it must first be 
acquired to a C2N-MNETGW gateway that is connected to a Cresnet network. 
NOTE: The -SW1RF, -SW4RF, -SWS1RF, and -SWS4RF can also work as stand-
alone wall box switches without being acquired by a C2N-MNETGW. 
NOTE: A switch can be acquired to only one gateway.
Acquire the Switch
To acquire a -SW1RF/-SW4RF/-SWS1RF/-SWS4RF to a C2N-MNETGW, perform 
the following: 
1. Put the C2N-MNETGW in the Acquire mode, from the unit itself or from
Crestron Toolbox, as described in the latest revision of the C2N-MNETGW 
Operations Guide (Doc. 6317) which is available from the Crestron website 
or the Crestron Toolbox help file. 
NOTE: In an environment where multiple gateways are installed, only one 
gateway should be in the Acquire mode at a time. 
2. Place
the
-SW1RF/-SW4RF/-SWS1RF/-SWS4RF into the Acquire mode by
doing the following:
a. Move the mode selection switch (located under the LED) to the
“OFF” position.
b. Press and hold the top or bottom of the button on the -SW1RF/
-SWS1RF or any button on the -SW4RF/-SWS4RF.
c. While holding the button, slide the mode selection switch to the
“RUN” position.
d. Hold the button for approximately five seconds until the LED
flashes HIGH once. Immediately release the button after the LED 
blinks to start the switch’s Acquire mode. 
NOTE: The LED can flash HIGH or LOW. Refer to “LED Behavior” on 
page 11 for more information. 
NOTE: Holding the button for a significant time after the first flash may 
enter other modes. If this is not desired, return the mode selection switch to 
the “OFF” position without releasing the button and repeat step 2. 
After approximately ten seconds, the LED will start to blink slowly and the 
switch will attempt to acquire with a C2N-MNETGW that is in the Acquire 
mode. The device is acquired when the LED stops blinking and lights at the 
LOW setting. After being acquired, the device will exit the Acquire mode. 
The switch will be acquired on the C2N-MNETGW with an MNET ID 
value of 01. If the switch was previously acquired on another infiNET 
network, the switch will be acquired on the C2N-MNETGW with its 
previous MNET ID. 
8
• infiNET Switches: Crestron CLW-SW1/4RF, -SWS1/4RF, -SLVS1RF
Operations Guide - DOC. 6397A