beautypg.com

Cleaning the combustion chamber and air, Diverter assembly, Awarning – Kenmore ELITE 153.33264 User Manual

Page 31

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Reposition the manifold component block in the mani-fold

door opening and secure it with the retainer clip.

See Replacing the Manifold/Burner Assembly.

External

Inspection

&

Cleaning

of

the

Air Intake Chamber Screen

1. At least twice annually inspect the air intake chamber screen

(Figure 38) for any dust or debris that may have accumulated
on the louvers. NOTE: If the water heater is located in an
area that is subjected to lint and dirt, it may be necessary to
check the air intake chamber screen
more frequently.

2. Use a vacuum cleaner with a hose

attachment to remove any dust or
debris that may have accumulated
on the screen.

Air Intake Chamb
Screen

FIGURE 38.

Cleaning the Combustion Chamber and Air

Diverter Assembly

1. Follow procedure outlined in “Removing the Manifold/Burner

Assembly”.

2. Use a vacuum cleaner/shop vac to remove all loose debris in

the combustion chamber (Figure 39). Use compressed air to
clear any dust or debris that may have accumulated on the
air diverter assembly.

Replacing the Manifold/Burner Assembly

Reassemble following the procedure under “Replacing the
Manifold/Burner Assembly”

AWARNING

U/

Explosion Hazard

Remove any fiberglass between gasket and

combustion chamber.

Replace viewport if glass is missing or damaged.

Replace two piece wire connector if missing or

removed.

Replace door gasket if damaged.

Tighten both manifold door screws securely.

Failure to follow these instructions can result in

death, explosion, or fire.

2

.

3.

4.

8

.

9.

Check the door gasket for damage or imbedded debris prior
to installation.

Inspect the view port for damage and replace as required.
Insert the manifold/burner assembly into the burner

compartment making sure that the tip of the manifold tube
engages in the slot of the bracket inside the combustion
chamber (Figure 40).

Inspect the door gasket and make sure there is no fiberglass
insulation between the gasket and the

combustion chamber.
Replace the two screws, which secure the manifold/
burner assembly door to the combustion chamber and
tighten securely. Once the manifold/burner assembly door
is tightened, visually inspect the door gasket between the
manifold/burner assembly door and the combustion chamber

for spaces or gaps that would prevent a seal. IMPORTANT:

Do not operate the water heater if the door gasket does not
create a seal between the manifold door and the combustion
chamber.
During the following procedure, do not cross-thread or apply
any thread sealant to any of the fittings listed below. First,
reconnect the manifold tubing to the gas control valve/

thermostat.

Reconnect the flame sense/hot surface igniter wire to the gas
control valve/thermostat (Figure 35).

Turn gas supply on and refer to the Lighting Instructions.
With the burner lit, check the gas control valve/thermostat
supply line, two piece wire connector, and manifold tube
connections for leaks. Check for leaks by brushing on an
approved noncorrosive leak detection solution.

IMPORTANT:

Do Not splash solution onto the electrical connections.

Bubbles forming indicate a leak. Correct any leak found. All
leaks must be fixed immediately.

31

This manual is related to the following products: