beautypg.com

Warning – Kenmore ELITE 153.33264 User Manual

Page 26

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Water Heater Operation

Checking the Draft

Figure 29 below shows the water heater’s sequence of operation

when a call for heat is initiated. The ignition control module will

attempt to light the burner three times. If the ignition control does
not detect ignition it will enter lockout mode, indicated by display

flashing status code (see status code 3 page 38 and/or status

code 8 page 39).

▲WARNING

Burn Hazard

Do not touch vent.

Doing so can result in burns.

SEQUENCE OF OPERATION

After successfully lighting the water heater, allow the unit to
operate for 15 minutes and check the draft hood relief opening
for proper draft (Figure 30). Make sure all other appliances in the

area are operating and all doors/windows are closed when
performing the draft test. Pass a match flame or smoke around
the relief opening of the draft hood. A steady flame or smoke
drawn into the opening indicates proper draft.

FIGURE 29.

Flue Products Vented

to Ouside of Building

Dilution Air

Draft Hood

Dilution Air

Match

Air is drawn in for
combustion. Keep
area clean and free
from combustibles
and flammable vapors.

6” Maximum

_J_ Air Gap

'Floor Drain

Outer Door

The water heater must be installed according to all local and state
codes or in the adsence of local and state codes, the “National Fuel
Code’” ANSI Z223.1 (NFPA 54)- current edition.

FIGURE 30.

If the flame flutters or is blown out, combustion products are escaping

from the relief opening. If this occurs, do not operate the water heater

until proper adjustments or repairs are made to the vent pipe system
and/or air supply requirements.

26

This manual is related to the following products: