Closed system/thermal expansion, Property damage hazard, Temperature and pressure relief valve – Kenmore ELITE 153.33264 User Manual
Page 22: Explosion hazard, Warning
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
!n a dosed system use a
/thermal expansion tank
Closed System/Thermal Expansion
Hot Water.
Outlet
Meta! Drain-..^r
Pan 1-3/4” ^
Depth Max.
Cold Water Supply^
to Fixture
Pressure Reducing
Valve v^ith Bypass
Main Water
Supply
Temperature and Pressure (T&P)
Relief Valve (Optional Top T&P
Relief Valve Not Shown)
Massachusetts:
Install a vacuum relief
in cold water line per
section 19 MGL 142
Discharge line
(Do Not Cap or Plug)
Drain
‘ Min.
Typical water piping installation
FIGURE 23.
FIGURE 24.
Please note the following:
•
The system should be installed only with piping that is suitable
for potable (drinkable) water such as copper, CPVC, or
polybutylene. This water heater must not be installed using
iron piping or PVC water piping.
•
Use only pumps, valves, or fittings that are compatible with
potable water.
•
It is recommend that only full flow ball or gate valves are used
in water piping installations. The use of valves that may cause
excessive restriction to water flow is not recommended.
•
Use only 95/5 tin-antimony or other equivalent solder. Any
lead based solder must not be used.
•
Piping that has been treated with chromates, boiler seal, or
other chemicals must not be used.
•
Chemicals that may contaminate the potable water supply
must not be added to the piping system.
f à l l l l Q l
Property Damage Hazard
All water heaters eventually leak
Do not install without adequate drainage.
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. The temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This condition is not covered
under the limited warranty.
A properly-sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Contact a plumbing service agency or your retail
supplier regarding the installation of a thermal expansion tank.
Temperature and Pressure Relief Valve
A
warning
Explosion Hazard
Temperature-pressure relief
valve must comply with ANSI
Z21.22-CSA4.4 and ASME
code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating
and excessive tank pressure.
Can cause serious injury or
death.
22