Timing module, Series 606 - programmable recycle, Timing diagram specifications – CAMCORP HVP with Roots Blower User Manual

Page 46

background image

AMERICAN CONTROL PRODUCTS

A DIV. OF PRECISION TIMER CO., INC.

47 WESTBROOK INDUSTRIAL PARK ROAD

WESTBROOK, CT. 06498

PHONE: (860)399-6253

FAX:(860)399-5619

EMAIL:[email protected]

Web Site: precisiontimer.com

TECHNICAL BULLETIN

SOLID STATE TIMING MODULE

PAGE 1
OF 2

DATE

6-4-01

606

REV

B

TIMING MODULE

FULLY SOLID STATE

ENCAPSULATED

ONE AMPERE LOAD RATING

Series 606 - PROGRAMMABLE RECYCLE

CMOS DIGITAL CIRCUITRY

Life Expectancy –unlimited

Environment Protected

Tamper Proof

No False Operate

Small Size – 2"x 2" x 53/64"

Lightweight – approximately 2.5
oz.

Rugged

E75633 LR46938

Application of power simultaneously initiates timing and turns the load ON. The load remains ON for the preset ON time period after which it
turns OFF for the preset OFF time period. The ON/OFF cycling continues until power is removed. Removal of power at any point in the cycle
will cause reset to T = To. The unit is available with the OFF time first, see the TIMING DIAGRAM and the table below.
Control the timing of valves, SFHP motors, lamps, relays, magnetic line starters, and actuators rated less than 1 ampere (10 amps inrush).
CMOS digital circuitry, with solid state output switching. P/C boards and internal components are encapsulated in a flame retardant molded
housing, fitted with quick connect wiring terminals. Available in all standard voltages and frequencies. Fixed or adjustable timing from .1 sec-
onds to 24 hours.

TIMING DIAGRAM

SPECIFICATIONS

1. Repeat Accuracy: ± 0.1% or 16 ms. Whichever is greater
2. Combined Effect of Temperature and Voltage upon Repeat Accuracy: 1%
3. Reset Time: 150 ms.
4. Operating Voltage Tolerance: ± 20%
5. Load Current: Steady State – 8 ma. Min., 1 Ampere Max., 10 A Inrush
6 Voltage Drop: 1.5V Typical at 1 Ampere
7. Leakage Current: 5 ma.
8. Dielectric Strength: 1500 VRMS
9. Insulation Resistance: 100 Megohms Min.
10. Input Transient Protection: 3000V 120V UNITS, 6000V 240V units
11. Temperature Ambients: Operating -40°C to +70°C, Storage -55°C to +70°C
12. Humidity-Operating: 95% Relative
13. Linearity(Option A or D ): ±5% Minimum from 10% to 90% of range
14. Timing Tolerance: ±9% + Tolerance of Rt Std., ±5% Special (Fixed)

EXAMPLE P/N: 606-325OC/240S This is an PROGRAMMABLE RECYCLE 1A Rated Solid State Timer with a 10-1000 second ADJUSTABLE ON TIME and a
fixed 240 second OFF TIME. The INPUT VOLTAGE of 120 VAC. The OFF TIME is FACTORY FIXED INTERNAL calibration. The customer will supply the ON
TIME adjust potentiometer or resistor

HOW TO ORDER

606 – (T1) (T2) (V) (P1) (P2)

SERIES

606

ON FIRST

606R

OFF FIRST

(T2) = OFF TIME

P = 0.1 - 5 SEC.

1 = 0.1 - 10 SEC.
L = 0.2 - 20 SEC.
J = 0.3 - 30 SEC.

M = 0.6 - 60 SEC.

2 = 1 - 100 SEC.

K = 1.2 - 120 SEC.

F = 2 - 180 SEC.
E = 3 - 300 SEC.

3 = 10 - 1000 SEC.

4 = O.1 - 10 MIN.
G = 0.3 - 30 MIN.
H = 0.6 - 60 MIN.

5 = 1 - 100 MIN.

V = 3 - 300 MIN.

6 = 10 - 1000 MIN.

D = 1 - 24 HRS.

(V)=VOLTAGE

1 = 12VDC

2 = 24VDC

3 = 48VDC
4 = 24VAC

5 = 120VAC

6 = 240VAC

OPTIONS (P1) = ON TIME, (P2) = OFF TIME

O - CUSTOMER SUPPLIES OWN POTENTIOMETER OR RESISTOR

A - POTENTIOMETER SUPPLIED AS LOOSE PART
*B - EXTERNALLY INSTALLED RESISTOR
*C - FACTORY FIXED INTERNAL
D - TRIMMER POTENTIOMETER INSTALLED ON TERMINALS
R - INTERNAL POTENTIOMETER WITH THRU SHAFT
S – INTERNAL POTENTIOMETER WITH SCREWDRIVER SLOT

* For Fixed Time Specify The Value In

Seconds, Minutes, Or Hours

MADE IN USA

(T1) = ON TIME

P = 0.1 - 5 SEC.

1 = 0.1 - 10 SEC.
L = 0.2 - 20 SEC.
J = 0.3 - 30 SEC.

M = 0.6 - 60 SEC.

2 = 1 - 100 SEC.

K = 1.2 - 120 SEC.

F = 2 - 180 SEC.
E = 3 - 300 SEC.

3 = 10 - 1000 SEC.

4 = O.1 - 10 MIN.
G = 0.3 - 30 MIN.
H = 0.6 - 60 MIN.

5 = 1 - 100 MIN.

V = 3 - 300 MIN.

6 = 10 - 1000 MIN.

D = 1 - 24 HRS.

606R (T1) (T2) (V) (P1) (P2)