Table 14 — Fan Performance (Air Foil) — 48/50MP70M*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
668
5.1
702
5.9
735
6.7
767
7.5
801
8.4
833
9.3
863
10.3
893
11.2
924
12.2
954
13.3
20,000
725
6.6
756
7.4
787
8.3
816
9.1
844
10.0
875
11.0
905
12.0
933
13.1
961
14.1
987
15.2
22,000
781
8.2
809
9.1
838
10.0
865
10.9
892
11.9
917
12.8
945
13.9
973
15.0
999
16.2
1025
17.3
24,000
837
10.0
864
11.0
890
12.1
916
13.1
941
14.1
966
15.1
989
16.2
1013
17.3
1039
18.5
1065
19.7
26,000
898
12.3
923
13.4
947
14.5
971
15.6
995
16.7
1018
17.8
1041
19.0
1063
20.1
1084
21.2
1108
22.5
28,000
955
14.8
979
16.0
1002
17.2
1025
18.4
1047
19.6
1069
20.8
1091
21.9
1112
23.1
1133
24.3
1153
25.6
30,000
1011
17.4
1034
18.8
1056
20.0
1078
21.3
1098
22.6
1119
23.9
1140
25.2
1160
26.5
1180
27.7
1200
29.0
32,000
1071
20.7
1093
22.1
1114
23.5
1135
24.9
1154
26.2
1174
27.6
1193
29.0
1213
30.4
1232
31.7
1251
33.1
34,000
1129
24.3
1150
25.7
1171
27.2
1190
28.7
1210
30.1
1228
31.6
1246
33.1
1264
34.6
1283
36.0
1301
37.4
36,000
1186
28.1
1207
29.6
1226
31.2
1245
32.8
1264
34.3
1282
35.9
1299
37.4
1317
39.0
1334
40.5
1351
42.1
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.00
3.25
3.50
3.75
4.00
4.25
4.50
4.75
5.00
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
983
14.3
1011
15.4
1039
16.4
1065
17.5
1091
18.6
—
—
—
—
—
—
—
—
20,000
1014
16.3
1042
17.4
1069
18.6
1095
19.7
1120
20.9
1145
22.1
1169
23.3
1193
24.5
1216
25.8
22,000
1050
18.5
1074
19.6
1098
20.8
1124
22.1
1149
23.3
1173
24.6
1197
25.9
1220
27.2
1243
28.5
24,000
1089
20.9
1113
22.2
1136
23.4
1158
24.7
1180
26.0
1202
27.3
1226
28.6
1249
30.0
1271
31.4
26,000
1132
23.8
1155
25.1
1177
26.4
1199
27.8
1221
29.1
1242
30.5
1262
31.9
1282
33.3
1303
34.7
28,000
1172
26.8
1195
28.2
1217
29.6
1239
31.0
1260
32.5
1280
33.9
1300
35.4
1320
36.8
1340
38.3
30,000
1219
30.3
1238
31.6
1256
32.9
1277
34.4
1298
35.9
1318
37.5
1338
39.0
1357
40.5
1376
42.1
32,000
1270
34.4
1288
35.8
1305
37.2
1323
38.6
1340
40.0
1360
41.6
1379
43.2
1398
44.8
1417
46.4
34,000
1319
38.9
1337
40.3
1354
41.8
1371
43.2
1388
44.7
1404
46.2
1420
47.7
1439
49.3
1457
51.0
36,000
1369
43.6
1386
45.1
1403
46.6
1419
48.2
1435
49.7
1451
51.3
1467
52.8
1483
54.4
1498
55.9
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 15 — Fan Performance (Air Foil) — 48/50MP82N*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
2.50
2.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
20,000
449
4.1
485
5.0
519
6.0
551
7.0
583
8.1
616
9.4
—
—
—
—
—
—
—
—
22,000
477
4.9
511
5.9
543
7.0
574
8.1
602
9.2
631
10.3
661
11.7
—
—
—
—
—
—
24,000
505
5.9
538
7.0
568
8.1
598
9.2
626
10.4
652
11.6
677
12.9
706
14.3
733
15.8
—
—
26,000
535
7.0
565
8.1
594
9.3
622
10.5
649
11.7
675
13.0
699
14.4
723
15.7
748
17.2
773
18.7
28,000
563
8.1
591
9.3
619
10.6
646
11.9
671
13.2
697
14.5
721
15.9
744
17.3
766
18.8
787
20.2
30,000
595
9.6
621
10.8
647
12.1
673
13.5
698
14.9
721
16.3
745
17.8
767
19.3
789
20.8
810
22.3
32,000
624
11.0
649
12.3
673
13.7
698
15.2
722
16.6
745
18.1
767
19.6
789
21.2
811
22.8
831
24.4
34,000
655
12.7
679
14.1
702
15.6
725
17.1
748
18.7
770
20.2
792
21.8
813
23.4
834
25.0
854
26.7
36,000
685
14.6
709
16.1
731
17.6
752
19.2
771
20.8
796
22.4
817
24.1
838
25.8
857
27.5
877
29.2
38,000
717
16.7
739
18.3
761
19.9
781
21.5
801
23.2
822
24.9
843
26.6
863
28.4
882
30.1
901
31.9
40,000
748
18.9
769
20.5
789
22.2
809
24.0
829
25.7
848
27.4
868
29.3
888
31.1
907
32.9
925
34.8
42,000
779
21.3
799
23.1
819
24.8
838
26.6
857
28.4
875
30.3
894
32.1
913
34.0
931
35.9
950
37.9
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.00
3.25
3.50
3.75
4.00
4.25
4.50
4.75
5.00
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
20,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
22,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
24,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
26,000
798
20.3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
28,000
812
21.9
835
23.6
858
25.3
—
—
—
—
—
—
—
—
—
—
—
—
30,000
831
23.8
851
25.4
874
27.2
896
29.1
917
30.9
—
—
—
—
—
—
—
—
32,000
851
26.0
871
27.6
890
29.3
910
31.0
931
32.9
952
34.9
972
36.8
992
38.8
—
—
34,000
874
28.4
893
30.1
912
31.8
930
33.6
948
35.3
966
37.2
986
39.2
1006
41.3
1025
43.4
36,000
896
31.0
915
32.7
934
34.5
952
36.3
969
38.2
986
40.0
1003
41.9
1021
43.8
1039
46.0
38,000
920
33.7
938
35.6
956
37.5
974
39.4
991
41.3
1008
43.2
1025
45.1
1041
47.1
1057
49.0
40,000
943
36.6
961
38.5
978
40.5
996
42.4
1013
44.4
1030
46.4
1046
48.4
1062
50.4
1078
52.5
42,000
967
39.8
984
41.8
1001
43.7
1018
45.8
1035
47.8
1052
49.9
1068
52.0
1084
54.0
1099
56.2
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
33