Table 5 — electrical data – Carrier 50MP62L-10R User Manual
Page 16

Table 5 — Electrical Data
UNIT
48MP/
50MP
VOLTAGE
3 Ph, 60 Hz
VOLTAGE
RANGE
COMP
NO. A1
COMP
NO. A2
COMP
NO. B1
COMP
NO. B2
CONDENSER
FAN
MOTORS
EVAPORATOR
FAN MOTOR
POWER
EXHAUST
FAN MOTOR
MCA
MOCP
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
RLA
LRA
Qty
FLA
Hp
FLA
Hp
FLA
Hp
62L
460
414
508
65.4
345
—
—
65.4
345
—
—
6
3.3
1
40
30
—
—
207.0
250
11
7.5
218.0
250
40
30
247.0
300
52
40
—
—
219.0
250
11
7.5
230.0
250
40
30
259.0
300
65
50
—
—
232.0
250
11
7.5
243.0
300
40
30
272.0
300
70M
460
414
508
46.8
253
34.6
173
65.4
345
—
—
6
3.3
1
52
40
—
—
235.0
300
11
7.5
246.0
300
52
40
287.0
350
65
50
—
—
248.0
300
11
7.5
259.0
300
52
40
300.0
350
77
60
—
—
262.9
300
11
7.5
273.9
350
52
40
314.9
350
82N
460
414
508
43.6
223
34.6
173
43.6
223
43.6
223
6
3.3
1
52
40
—
—
250.2
300
11
7.5
261.2
300
52
40
302.2
350
65
50
—
—
266.5
300
11
7.5
277.5
300
52
40
318.5
350
77
60
—
—
281.5
350
11
7.5
292.5
350
52
40
333.5
400
90P
460
414
508
43.6
223
46.8
253
43.6
223
46.8
253
8
3.3
1
65
50
—
—
288.5
350
14
10
302.5
350
65
50
353.5
350
77
60
—
—
303.5
350
14
10
317.5
350
65
50
368.5
400
96
75
—
—
327.5
400
14
10
341.5
400
65
50
392.2
450
10R
460
414
508
43.6
223
65.4
345
43.6
223
46.8
253
8
3.3
1
65
50
—
—
307.2
350
14
15
321.1
350
77
60
387.1
450
77
60
—
—
322.1
350
14
15
336.1
400
77
60
399.1
450
96
75
—
—
345.8
400
14
15
359.8
450
77
60
422.8
500
LEGEND
COMP — Compressor
FLA
— Full Load Amps
Hp
— Nominal Horsepower
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps (for wire sizing)
MOCP — Maximum Overcurrent Protection
RLA
— Rated Load Amps
16