Table 10 — Fan Performance (Forward Curved) — 48/50MP82N*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
293
6.2
326
7.7
359
9.3
392
11.2
425
13.2
457
15.3
24,000
308
7.6
339
9.1
369
10.8
399
12.7
429
14.7
459
16.9
26,000
324
9.2
352
10.8
380
12.6
408
14.5
436
16.6
464
18.8
28,000
341
11.0
367
12.7
393
14.6
419
16.5
445
18.7
471
20.9
30,000
358
13.1
382
14.9
407
16.8
431
18.9
455
21.1
480
23.4
32,000
375
15.5
398
17.4
421
19.4
444
21.5
467
23.8
490
26.2
34,000
393
18.2
415
20.2
436
22.3
458
24.5
479
26.8
501
29.3
36,000
411
21.2
432
23.3
452
25.5
473
27.8
493
30.2
513
32.7
38,000
430
24.6
449
26.8
468
29.1
488
31.4
507
33.9
526
36.5
40,000
448
28.3
467
30.6
485
33.0
504
35.5
522
38.1
540
40.7
42,000
467
32.5
485
34.9
502
37.3
520
39.9
537
42.6
555
45.4
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.00
2.25
2.50
2.75
3.00
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
462
15.0
489
16.8
515
18.7
541
20.7
567
22.9
24,000
466
16.6
491
18.5
516
20.4
540
22.4
564
24.5
26,000
472
18.6
495
20.4
519
22.3
542
24.4
564
26.5
28,000
480
20.8
502
22.7
524
24.6
546
26.7
567
28.8
30,000
489
23.4
510
25.3
531
27.2
551
29.3
572
31.4
32,000
500
26.2
520
28.1
539
30.2
559
32.2
578
34.4
34,000
512
29.4
530
31.4
549
33.4
568
35.5
586
37.7
36,000
524
32.9
542
34.9
560
37.0
578
39.2
595
41.4
38,000
538
36.8
555
38.9
572
41.0
589
43.2
605
45.5
40,000
552
41.0
568
43.2
584
45.4
601
47.7
617
50.0
42,000
567
45.7
582
47.9
598
50.2
613
52.5
629
54.9
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 11 — Fan Performance (Forward Curved) — 48/50MP90P*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
297
6.9
329
7.9
360
8.9
375
9.8
402
11.4
430
13.0
24,000
313
8.5
343
9.6
371
10.7
395
11.7
420
13.2
445
14.8
26,000
330
10.3
357
11.5
384
12.7
410
13.8
430
15.3
452
16.9
28,000
347
12.3
373
13.6
398
14.9
422
16.2
442
17.4
462
19.0
30,000
365
14.6
389
16.0
412
17.4
436
18.8
449
19.8
469
21.4
32,000
381
16.5
400
17.9
420
19.4
440
21.0
460
22.7
480
24.5
34,000
400
19.4
418
20.9
437
22.4
455
24.1
474
25.8
493
27.6
36,000
419
22.6
437
24.2
454
25.8
472
27.5
489
29.3
507
31.2
38,000
439
26.2
455
27.9
472
29.6
488
31.3
505
33.2
522
35.1
40,000
458
30.3
474
32.0
490
33.7
505
35.5
521
37.4
537
39.4
42,000
478
34.7
493
36.4
508
38.3
523
40.2
538
42.1
553
44.1
44,000
498
39.5
512
41.3
527
43.2
541
45.2
555
47.2
570
49.3
46,000
518
44.8
532
46.7
546
48.7
559
50.7
573
52.8
587
54.9
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.00
2.25
2.50
2.75
3.00
3.25
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
22,000
455
14.5
480
16.0
506
17.8
532
19.5
555
21.5
578
23.5
24,000
465
16.4
485
18.0
515
20.0
545
22.0
568
23.8
590
25.5
26,000
475
18.5
500
20.5
525
22.5
548
24.5
570
26.2
590
28.0
28,000
486
20.8
510
22.5
531
24.5
552
26.5
572
28.5
592
30.5
30,000
488
23.0
510
24.8
532
26.5
552
28.6
572
30.8
590
33.0
32,000
501
26.3
522
28.3
542
30.4
563
32.5
585
34.8
602
36.5
34,000
512
29.5
532
31.5
551
33.6
571
35.8
590
38.1
610
40.4
36,000
525
33.1
543
35.1
561
37.2
580
39.4
598
41.7
617
44.1
38,000
539
37.1
556
39.1
573
41.2
590
43.5
607
45.7
625
48.1
40,000
553
41.4
569
43.5
585
45.7
602
47.9
618
50.2
634
52.6
42,000
568
46.2
584
48.3
599
50.5
614
52.8
630
55.2
645
57.6
44,000
584
51.4
599
53.6
613
55.8
628
58.2
642
60.6
657
63.0
46,000
600
57.1
614
59.3
628
61.6
642
64.0
656
66.4
670
68.0
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on
48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
31