Table 8 — Fan Performance (Forward Curved) — 48/50MP62L*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
16,000
346
3.4
382
4.1
415
5.0
448
6.0
478
7.2
508
8.6
18,000
371
4.7
404
5.5
436
6.4
466
7.4
494
8.6
522
10.0
20,000
398
6.3
428
7.2
458
8.2
486
9.3
513
10.5
539
11.9
22,000
426
8.4
454
9.4
481
10.5
508
11.6
533
12.9
558
14.3
24,000
455
11.0
481
12.1
506
13.3
531
14.5
555
15.8
578
17.3
26,000
484
14.2
508
15.4
532
16.6
555
18.0
578
19.4
600
20.9
28,000
514
18.0
537
19.3
559
20.7
581
22.1
602
23.6
623
25.2
30,000
544
22.5
566
23.9
587
25.4
608
26.9
628
28.5
648
30.2
32,000
575
27.9
595
29.4
615
30.9
635
32.6
654
34.3
673
36.1
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.00
2.25
2.50
2.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
16,000
536
10.1
563
11.9
590
13.9
615
16.0
18,000
549
11.5
575
13.2
600
15.1
624
17.1
20,000
564
13.4
589
15.1
613
16.9
636
18.9
22,000
582
15.8
605
17.5
628
19.3
650
21.3
24,000
601
18.9
623
20.6
645
22.4
666
24.3
26,000
622
22.5
643
24.3
664
26.1
684
28.1
28,000
644
26.9
664
28.7
684
30.6
703
32.6
30,000
667
32.0
686
33.9
705
35.8
724
37.9
32,000
692
38.0
710
39.9
728
42.0
746
44.1
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on 48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.
Table 9 — Fan Performance (Forward Curved) — 48/50MP70M*
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.50
0.75
1.00
1.25
1.50
1.75
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
365
6.4
398
7.4
432
8.5
465
9.8
499
11.1
532
12.6
20,000
391
8.2
421
9.3
451
10.4
482
11.7
512
13.1
542
14.5
22,000
418
10.4
446
11.5
473
12.7
501
14.0
528
15.4
556
16.9
24,000
447
12.9
472
14.1
497
15.4
523
16.8
548
18.2
573
19.7
26,000
476
15.9
499
17.2
523
18.6
546
20.0
569
21.5
592
23.0
28,000
506
19.4
527
20.8
549
22.2
571
23.6
592
25.2
614
26.8
30,000
536
23.4
556
24.8
576
26.3
596
27.8
617
29.4
637
31.0
32,000
566
27.9
585
29.4
604
30.9
623
32.5
642
34.2
661
35.9
34,000
597
32.9
615
34.5
633
36.1
651
37.8
668
39.5
686
41.3
36,000
628
38.6
645
40.2
662
41.9
679
43.7
695
45.4
712
47.3
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
2.00
2.25
2.50
2.75
300
325
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
18,000
565
14.2
598
16.0
631
17.8
664
19.9
696
22.1
729
24.4
20,000
572
16.1
602
17.8
631
19.6
661
21.5
691
23.6
720
25.8
22,000
583
18.5
610
20.2
638
21.9
665
23.8
692
25.8
719
27.9
24,000
598
21.3
623
23.0
648
24.7
673
26.6
698
28.5
723
30.6
26,000
616
24.6
639
26.3
662
28.1
685
29.9
708
31.9
731
33.9
28,000
635
28.4
657
30.1
679
31.9
700
33.8
722
35.7
743
37.7
30,000
657
32.7
677
34.5
697
36.3
717
38.2
737
40.2
758
42.2
32,000
680
37.6
699
39.4
718
41.3
737
43.2
756
45.2
774
47.2
34,000
704
43.1
722
44.9
740
46.8
757
48.8
775
50.8
793
52.9
36,000
729
49.1
746
51.0
763
53.0
780
55.0
796
57.1
813
59.2
LEGEND
Bhp — Brake Horsepower
*Refer to Fan Performance, 48MP Units section, for correct procedure on 48MP units.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. Conversion — Bhp to kW:
Bhp × .746
kW =
Motor efficiency
See Table 1 for motor efficiency.