5 | electrical connection – GEA Bock HGX46 CO2 T User Manual

Page 19

background image

D
GB
F
E

19

96259-12.2014-DGb

In the factory, the motor is switched for direct starting (YY). For part winding start (Y/YY), remove the
bridges and connect the motor feed cable according to the circuit diagram:

400 V

Direct start YY

Part winding start Y/YY

L1

L2

L3

L1

L2

L3

L1

L3

L2

PTC

PW

II

PW

I

PTC

ATTENTION Property damage possible.

Failure to comply results in reversed fields of rotation and can
cause motor damage. After the motor has started up with part win-
ding 1, part winding 2 must be switched on after max. 1 second
delay. Failure to comply can be detrimental to the service life of
the motor.
Ensure that power is supplied via K1 to winding 1 (66%) (1U1 /
1V1 / 1W1) and via K2 to winding 2 (33%) (2U1 / 2V1 / 2W1). The
motor contactors (K1/K2) are each to be rated for approx. 70% of
the max. operating current.

5| Electrical connection