7.1 Preparation

7 | Maintenance

WARNING! Before starting any work on the compressor:

Switch off the compressor and secure it to prevent a restart.

Close all shut-off valves.

Relieve compressor of system pressure.

Prevent air from infiltrating the system!

After maintenance has been performed:

Connect safety switch.

Evacuate compressor.

Open all shut-off valves.

Function of the safety devices guarantee.

Release switch-on lock..

HGX2/ ... CO

2

T

70-4

90-4

110-4

130-4

Designation

Item No.

Item No.

Item No.

Item No.

Set of gaskets

80538

Set of valve plate kit

80532

80533

Set of piston/connecting rod

80508

80528

80529

Set of connecting rod

80520

Only use genuine GEA Bock spare parts!

7.3 Spare part recommendation

7.2 Work to be carried out
In order to guarantee optimum operational reliability and service life of the compressor,

we recommend

carrying out servicing and inspection work at regular intervals:

Oil change:

-

not mandatory for factory-produced series systems.

-

for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.

Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.

Available accessories can be found on the Internet at www.gea.com

7.4 Accessories

WARNING! The selected duration for pressure relief must be long enough to

prevent the formation of dry or solid ice that can close the outlet

port and stop all the CO

2

from being discharged. Otherwise, there is

a risk of the compressor remaining in a hazardous operating

pressure.