6.8 Avoid slugging

ATTENTION! Slugging can result in damage to the compressor and cause

refrigerant to leak.

To prevent slugging:

The complete refrigeration plant must be properly designed.
All components must be compatibly rated with each other with regard to output (particularly the

evaporator and expansion valves).

Suction gas superheating at the compressor input

should be > 10 K (check the setting of the

expansion valve).

The system must reach a state of equilibrium.
Particularly in critical systems (e.g. several evaporator points), measures such as the use of liquid

traps, solenoid valve in the liquid line, etc. are recommended.
There should be no movement of refrigerant in the compressor while the system is at a
standstill.