6.8 Avoid slugging
 ATTENTION! Slugging can result in damage to the compressor and cause 
		
refrigerant to leak.
To prevent slugging:
 The complete refrigeration plant must be properly designed.
 All components must be compatibly rated with each other with regard to output (particularly the 
evaporator and expansion valves).
Suction gas superheating at the compressor input
should be > 10 K (check the setting of the
expansion valve).
	 The	system	must	reach	a	state	of	equilibrium.	
	 	Particularly	in	critical	systems	(e.g.	several	evaporator	points),	measures	such	as	the	use	of	liquid	
traps,	solenoid	valve	in	the	liquid	line,	etc.	are	recommended.	 
There should be no movement of refrigerant in the compressor while the system is at a 
 standstill.