beautypg.com

Dip switch settings – Steffes Transmitter User Manual

Page 8

background image

I

NSTALLATION

C

ONTINUED

Anticipated Peak

Typically, power companies are capable of sending one signal for peak

control of selected devices. There are some instances; however, where

power companies are capable of sending multiple signals for control

purposes. In these situations, it is possible to have on-peak hours, off-peak

hours, and anticipated peak (pre-peak) hours.
On-peak hours are times during which a controllable load is disabled.

Off-peak hours are times during which a controllable load is allowed to

operate.

Anticipated (pre-peak) hours are times during which ETS

equipment can be prepared for an up coming on-peak (control) period, or a

time when power companies can apply customized control of the ETS

equipment.
Power companies selectively use anticipated peak (pre-peak) signals. If

uncertain as to whether this option is being utilized in your area, contact

your local power company representative.

DIP SWITCH SETTINGS

If the transmitter is being utilized with the Steffes 1000 and/or 2000 Series

heater(s), all dip switches on the heater’ s main control circuit board MUST

be set to the “ OFF” position except dip switches 5 and 7. These can be in

the “ OFF” or “ ON” position, depending on the application.

DIP SWITCH 1: INVERT PEAK

This dip switch is used to match the Steffes 1000, 2000, 2100 Series

room heaters, the Comfort Plus, or any device wired to the Steffes PLC

receiver for peak control purposes to the utility’ s signaling device.

FACTORY DEFAULT SETTING = ON

Off = An open utility switch signals an off-peak time to the heater

(charging is enabled in the ETS heater). A closed utility switch

signals an on-peak time (charging is disabled in the ETS

heater).

On = A closed utility switch signals an off-peak time to the heater

(charging is enabled in the ETS heater). An open utility switch

signals an on-peak time (charging is disabled in the ETS

heater).

D

IP

S

WITCH

S

ETTINGS

C

ONTINUED

… .

DIP SWITCH 2, 3, 4 and 5: TRANSMIT CHANNEL

The transmitter is capable of transmitting on one of fifteen channels. The

dip switch settings in the Steffes PLC transmitter MUST be set to match

the channel setting of the receiving device(s).
To select the power line carrier communication channel desired, use the

chart below and set dip switches 2, 3, 4 and 5 to the appropriate positions.

If dip switch 2, 3, 4, and 5 are all set to the "OFF" positions, the

transmitter will not transmit a power line carrier signal.

FACTORY DEFAULT = Channel One (2 ON, 3 OFF, 4 OFF, 5 OFF)

C

HANNEL

D

IP

S

WITCH

#2

D

IP

S

WITCH

#3

D

IP

S

WITCH

#4

D

IP

S

WITCH

#5

C

HANNEL

S

PEED

0

OFF

OFF

OFF

OFF

N/A

1

ON

OFF

OFF

OFF

SLOW

2

OFF

ON

OFF

OFF

SLOW

3

ON

ON

OFF

OFF

FAST

4

OFF

OFF

ON

OFF

FAST

5

ON

OFF

ON

OFF

FAST

6

OFF

ON

ON

OFF

FAST

7

ON

ON

ON

OFF

FAST

8

OFF

OFF

OFF

ON

FAST

9

ON

OFF

OFF

ON

FAST

10

OFF

ON

OFF

ON

FAST

11

ON

ON

OFF

ON

FAST

12

OFF

OFF

ON

ON

SLOW

13

ON

OFF

ON

ON

SLOW

14

OFF

ON

ON

ON

SLOW

15

ON

ON

ON

ON

SLOW

1. 1000/2000 Series heaters will ONLY receive on slow speed

channels.

2. If multiple transmitters are installed on the same

distribution transformer, do not use both channels one (1)

and two (2).

4

5