Fire or Explosion

Hazard

Can cause severe injury, death,

or property damage.

Replacement control must be configured

to match all timings, settings, and pre-

purge of the control being replaced.

DO NOT USE A TRIAL FOR

IGNITION TIMING LONGER

THAN THE TIMING ON THE

ORIGINAL CONTROL. Severe

injury, death, or substantial

property damage could result from

a longer trial for ignition timing.

MATCH THE LOCKOUT LOGIC

SEQUENCE TO THE ORIGINAL

CONTROL. If the original control

is a single trial for ignition or

allows three trials for ignition

before lockout, the replacement

control must match the number of

ignition trials.

Operation

7590T

The 7590T may replace some existing burner

controls designed for 24 volt gas valves. The

7590T cannot be used to replace controls

designed for use with line voltage (120 Vac)

gas valves or controls with pressure switch

connections.

Settings are locked after 4

hours of burner operation.

Status & Diagnostics

The 7590 module has 3 LED lights

Wiring must comply with all national and

local codes. Wiring must follow appliance

and burner manufacturer’s instructions.

Follow the appropriate hook up drawing

for the application in which the control is

being installed.

The ignition cable length

should be 3 feet or less,

or meet igniter manufacturer’s specified

length. Avoid placing the ignition cable in

direct contact with metal surfaces as

reduced spark voltage could result. Use

plastic or ceramic standoffs if necessary.

The control, electrode

and flame sensor must

have a common ground with the main

burner for proper operation. Failure to

provide proper ground for the control,

electrode and sensor may result in a failure

to sense the presence of flame. Failure to

sense flame will result in lockout or

continued cycling of the ignition sequence.

On models with Air

Pressure Switch

terminals (7590C, D), do not place a

jumper on the Air Pressure Switch

terminals. Placing a jumper on the

terminals will cause the control to lockout.

The Air Pressure Switch must be in place

for the control to operate properly

Frozen Plumbing

and Water

Damage Hazard

If the residence is unattended in

severely cold weather, burner primary

control safety lockout, heating system

component failures, power outages or

other electrical system failures could

result in frozen plumbing and water

damage in a matter of hours.
For protection, take preventive actions

such as having a security system installed

that operates during power outages,

senses low temperature and initiates an

effective action. Consult with your heating

contractor or a home security agency.

Fire or Explosion

Hazard

Can cause severe injury, death,

or property damage.

USE 7590 GAS BURNER CONTROL ONLY

WITH BECKETT 7474001 GAS IGNITER.
Use with other igniters could result in

allowing gas flow when flame is not

present.