Information chart – Beckett 61687 GeniSys Display and Contractor Tool User Manual

Page 10

background image

10

Screen Message

Sensor/Monitor/

Message

Notes/Checks

### ohms avg

Cad Cell

Historical cycle data located in Control. Average Cad Cell resis-
tance measurement during burner operation.

### ohms max

Cad Cell

Historical cycle data located in Control. Maximum Cad Cell
resistance measurement during burner operation.

##:## run time

Timer

Historical cycle data located in Control. Indicates burner run
time.

##:## to light

Timer/Cad Cell

Historical cycle data located in Control. This value is the time
elapsed prior to the Cad cell resistance indicating a fl ame in the
chamber.

avg ### v

Line voltage (L1)

Historical cycle data located in Control. Average line voltage
measurement during burner operation.

Did Not Light

Cad Cell

Historical cycle data located in Control. Message indicates the
Cad cell did not detect a fl ame during trial for ignition.

Heat Call End

Thermostat or Limit

Inputs

Historical cycle data located in Control. Indicates the cycle
ended when an open circuit was detected in the T-T or Limit
circuit.

Lifetime Cycles

Counter

Counter located in Control, can not be reset and does not
require Display to function. Display required to monitor.

Lost Flame

Cad Cell

Historical cycle data located in Control. Message indicates that
the control locked out after the burner attempted to recycle
multiple times.

Low voltage

Line voltage (L1)

Historical cycle data located in Control. Indicates the cycle
ended when the line voltage dropped below approximately 78
volts.

Manual Shutdown

Reset button pressed

Historical cycle data located in Control. Indicates the cycle
ended when the Reset button was pressed.

Pre-Time Flame

Cad Cell

Historical cycle data located in Control. Message indicates the
cycle ended because the Cad cell detected a fl ame during the
Pre-time function.

Pump Prime

Reset button pressed

>15 seconds

Real-time indication of the burner functioning in the pump prime
mode.

Recycled

Cad Cell

Historical cycle data located in Control. Indicates the Cad cell
detected a loss of fl ame. Control starts 60 second time delay
then initiates a new cycle if there is a call for heat.

Replace Control

Historical cycle data located in Control. Control runs a continu-
ous self-check and will display this message if a cycle ended
after detecting an internal malfunction.

Service Messages

Technician entered

Located in Display. When the burner is in hard lockout the dis-
play fl ashes between the customized message and the reason
for the lockout.

Since Cleared Cycles

Counter

Counter located in Display, reset from display.

Since Cleared Hours

Timer

Timer located in Display, reset from display.

Information Chart